Set the derivative multiplier to counteract overshoot
and droop during changes in the room load. Measured
in %/(C / min).
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Set the derivative multiplier to counteract overshoot
and droop during changes in the room load. Measured
in %/(C / min).
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airFMSysCoolPIDDerivativeD OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Set the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysCooling 23 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysCoolPIDDerivativeD OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Set the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysCooling 23 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.5.23.0 | airFMSysCoolPIDDerivativeD | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.5.1 | airFMSysCompMinOnTime | 1 | 1 | Set the minimum time the compressor continues to operate after it is started. The delay protects the compressor from damage. Caut… |
1.3.6.1.4.1.318.1.1.13.1.4.5.2 | airFMSysCompMinOffTime | 1 | 1 | airFMSysCompMinOfftime |
1.3.6.1.4.1.318.1.1.13.1.4.5.3 | airFMSysCompRotPeriod | 1 | 1 | Set how often to perform compressor runtime balancing. Measured in hours. A value of -2147483648 indicates that this OID does not… |
1.3.6.1.4.1.318.1.1.13.1.4.5.4 | airFMSysEconIsolVlvOpenDelay | 1 | 1 | Set the delay between opening the Economizer Isolator output relay and engaging the compressors. Measured in seconds. A value of … |
1.3.6.1.4.1.318.1.1.13.1.4.5.5 | airFMSysEconIsolVlvCloseDelay | 1 | 1 | Set the delay between disengaging the compressor and closing the Economizer Isolator output relay. Measured in seconds. A value of… |
1.3.6.1.4.1.318.1.1.13.1.4.5.6 | airFMSysCndsrFluidVlvCloseDelay | 1 | 1 | Set the time the condenser valve remains open after the compressors disengage. Measured in seconds. A value of -2147483648 indic… |
1.3.6.1.4.1.318.1.1.13.1.4.5.7 | airFMSysInterstageDelay | 1 | 1 | The DX interstage delay allows the first compressor's cooling to take effect before engaging the second compressor. This prevents… |
1.3.6.1.4.1.318.1.1.13.1.4.5.8 | airFMSysCoolState | 1 | 1 | Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they ar… |
1.3.6.1.4.1.318.1.1.13.1.4.5.9 | airFMSysCoolEssFunction | 1 | 1 | Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during no… |
1.3.6.1.4.1.318.1.1.13.1.4.5.10 | airFMSysCoolSetpointC | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heat… |
1.3.6.1.4.1.318.1.1.13.1.4.5.11 | airFMSysCoolSetpointF | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heat… |
1.3.6.1.4.1.318.1.1.13.1.4.5.12 | airFMSysCoolDeadbandC | 1 | 1 | The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this… |
1.3.6.1.4.1.318.1.1.13.1.4.5.13 | airFMSysCoolDeadbandF | 1 | 1 | The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this… |
1.3.6.1.4.1.318.1.1.13.1.4.5.14 | airFMSysCoolEconIsolFunction | 1 | 1 | Set the Economizer Automatic Coolant Isolation valve to enabled or disabled. This valve anticipates a cooling demand and opens th… |
1.3.6.1.4.1.318.1.1.13.1.4.5.15 | airFMSysSuctPresCompensation | 1 | 1 | Set the Suction Pressure Compensation to enabled or disabled. This function attempts to keep the suction pressure from exceeding … |
1.3.6.1.4.1.318.1.1.13.1.4.5.16 | airFMSysCoilFluidActivThreshC | 1 | 1 | The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Celsius… |
1.3.6.1.4.1.318.1.1.13.1.4.5.17 | airFMSysCoilFluidActivThreshF | 1 | 1 | The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Fahrenh… |
1.3.6.1.4.1.318.1.1.13.1.4.5.18 | airFMSysCoilFluidActivDeadbandC | 1 | 1 | The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature ac… |
1.3.6.1.4.1.318.1.1.13.1.4.5.19 | airFMSysCoilFluidActivDeadbandF | 1 | 1 | The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature ac… |
1.3.6.1.4.1.318.1.1.13.1.4.5.20 | airFMSysCoolPIDMethod | 1 | 1 | Set the multipliers that the PID algorithm will use to calculate the cool output. Proportional, Proportional + Integral, or Propo… |
1.3.6.1.4.1.318.1.1.13.1.4.5.21 | airFMSysCoolPIDGainP | 1 | 1 | Set the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoin… |
1.3.6.1.4.1.318.1.1.13.1.4.5.22 | airFMSysCoolPIDResetRateI | 1 | 1 | Set the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates th… |