Set the priority of the mode for alarms and events
with the nonessential stop behavior. Nonessential
modes are disabled during nonessential stop alarms
and events.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Set the priority of the mode for alarms and events
with the nonessential stop behavior. Nonessential
modes are disabled during nonessential stop alarms
and events.
A value of notApplicable indicates that this OID does
not apply to this device due to its configuration.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airFMSysReheatEssFunction OBJECT-TYPE SYNTAX INTEGER { notApplicable (1), yes (2), no (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysReheat 2 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysReheatEssFunction OBJECT-TYPE SYNTAX INTEGER { notApplicable (1), yes (2), no (3) } ACCESS read-write STATUS mandatory DESCRIPTION "Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysReheat 2 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.8.2.0 | airFMSysReheatEssFunction | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.8.1 | airFMSysReheatState | 1 | 1 | Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they ar… |
1.3.6.1.4.1.318.1.1.13.1.4.8.3 | airFMSysReheatSetpointC | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 C below the cooling setpoint. Measur… |
1.3.6.1.4.1.318.1.1.13.1.4.8.4 | airFMSysReheatSetpointF | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 C below the cooling setpoint. Measur… |
1.3.6.1.4.1.318.1.1.13.1.4.8.5 | airFMSysReheatDeadbandC | 1 | 1 | The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of t… |
1.3.6.1.4.1.318.1.1.13.1.4.8.6 | airFMSysReheatDeadbandF | 1 | 1 | The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of t… |
1.3.6.1.4.1.318.1.1.13.1.4.8.7 | airFMSysReheatPIDMethod | 1 | 1 | Set the multipliers that the PID algorithm will use to calculate the output. Proportional, Proportional + Integral, or Proportion… |
1.3.6.1.4.1.318.1.1.13.1.4.8.8 | airFMSysReheatPIDGainP | 1 | 1 | Set the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoin… |
1.3.6.1.4.1.318.1.1.13.1.4.8.9 | airFMSysReheatPIDResetRateI | 1 | 1 | Set the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates th… |
1.3.6.1.4.1.318.1.1.13.1.4.8.10 | airFMSysReheatPIDDerivativeD | 1 | 1 | Set the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value… |