Reference record for OID 1.3.6.1.4.1.318.1.1.13.1.4.8.6



parent
1.3.6.1.4.1.318.1.1.13.1.4.8 (airFMSysReheat)
node code
6
node name
airFMSysReheatDeadbandF
dot oid
1.3.6.1.4.1.318.1.1.13.1.4.8.6
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysReheat(8) airFMSysReheatDeadbandF(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysReheat(8) airFMSysReheatDeadbandF(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysReheat(8) airFMSysReheatDeadbandF(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysReheat(8) airFMSysReheatDeadbandF(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysReheat(8) airFMSysReheatDeadbandF(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysReheat(8) airFMSysReheatDeadbandF(6)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysReheat/airFMSysReheatDeadbandF
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysReheat/airFMSysReheatDeadbandF
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysReheat/airFMSysReheatDeadbandF
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysReheat/airFMSysReheatDeadbandF
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysReheat/airFMSysReheatDeadbandF
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysReheat/airFMSysReheatDeadbandF
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/13/1/4/8/6

    Description by mibdepot

    The temperature range that controls output when the
    selected control sensor temperature is below the
    setpoint. At the bottom of this range, the reheat
    mode outputs at 100%. The deadband does not apply to
    PID-controlled modes. Measured in tenths of degrees
    Fahrenheit.
    A value of -2147483648 indicates that this OID does
    not apply to this device due to its configuration.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    The temperature range that controls output when the
    selected control sensor temperature is below the
    setpoint. At the bottom of this range, the reheat
    mode outputs at 100%. The deadband does not apply to
    PID-controlled modes. Measured in tenths of degrees
    Fahrenheit.
    A value of -2147483648 indicates that this OID does
    not apply to this device due to its configuration.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    airFMSysReheatDeadbandF OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysReheat 6 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    airFMSysReheatDeadbandF OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysReheat 6 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.13.1.4.8.6.0 airFMSysReheatDeadbandF 0 0 None

    Brothers (9)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.13.1.4.8.1 airFMSysReheatState 1 1 Set the mode to enabled or disabled. Disabled modes
    will not operate, and you cannot make changes to their
    settings while they ar…
    1.3.6.1.4.1.318.1.1.13.1.4.8.2 airFMSysReheatEssFunction 1 1 Set the priority of the mode for alarms and events
    with the nonessential stop behavior. Nonessential
    modes are disabled during no…
    1.3.6.1.4.1.318.1.1.13.1.4.8.3 airFMSysReheatSetpointC 1 1 The target value for the selected control sensor air
    for this mode. It must be at least 1.0 C below the
    cooling setpoint. Measur…
    1.3.6.1.4.1.318.1.1.13.1.4.8.4 airFMSysReheatSetpointF 1 1 The target value for the selected control sensor air
    for this mode. It must be at least 1.0 C below the
    cooling setpoint. Measur…
    1.3.6.1.4.1.318.1.1.13.1.4.8.5 airFMSysReheatDeadbandC 1 1 The temperature range that controls output when the
    selected control sensor temperature is below the
    setpoint. At the bottom of t…
    1.3.6.1.4.1.318.1.1.13.1.4.8.7 airFMSysReheatPIDMethod 1 1 Set the multipliers that the PID algorithm will use
    to calculate the output. Proportional,
    Proportional + Integral, or Proportion…
    1.3.6.1.4.1.318.1.1.13.1.4.8.8 airFMSysReheatPIDGainP 1 1 Set the proportional multiplier to correct for
    differences between the selected control sensor
    actual temperature and the setpoin…
    1.3.6.1.4.1.318.1.1.13.1.4.8.9 airFMSysReheatPIDResetRateI 1 1 Set the integral multiplier to correct for the
    proportional offset. Measured in %/(C * min).
    A value of -2147483648 indicates th…
    1.3.6.1.4.1.318.1.1.13.1.4.8.10 airFMSysReheatPIDDerivativeD 1 1 Set the derivative multiplier to counteract overshoot
    and droop during changes in the room load. Measured
    in %/(C / min).
    A value…