Reference record for OID 1.3.6.1.4.1.318.1.1.14.3.3.1.7
- Parent
- 1.3.6.1.4.1.318.1.1.14.3.3.1 (rARUStatusEntry)
- Node code
- 7
- Node name
- rARUStatusAruTemp3
- Numeric OID
- 1.3.6.1.4.1.318.1.1.14.3.3.1.7
- URN notation
- urn:oid:1.3.6.1.4.1.318.1.1.14.3.3.1.7
- Type
- OBJECT-TYPE
- ASN.1 notation
-
{1 3 6 1 4 1 318 1 1 14 3 3 1 7}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) rARU(14) rARUStatus(3) rARUStatusTable(3) rARUStatusEntry(1) rARUStatusAruTemp3(7)}
- OID-IRI notation
- /1/3/6/1/4/1/318/1/1/14/3/3/1/7
- /ISO/Identified-Organization/6/1/4/1/318/1/1/14/3/3/1/7
- /ISO/3/6/1/4/1/318/1/1/14/3/3/1/7
- Named path variants
- /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/enterprise/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/enterprises/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/ldap-enterprise/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/vendor-objects/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/identified-organization/dod/internet/private/vendor-objects/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/enterprise/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/enterprise/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/enterprises/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/enterprises/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/ldap-enterprise/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/ldap-enterprise/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/vendor-objects/apc/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- /iso/org/dod/internet/private/vendor-objects/PDU/products/hardware/rARU/rARUStatus/rARUStatusTable/rARUStatusEntry/rARUStatusAruTemp3
- Additional combinations skipped.
Descriptions
Descriptions may differ between sources. The primary description is shown first.
Primary description: Circitor
The exhaust temperature in the lower plenum on 2nd generation ARUs.
NOTE: -1 will be returned if the ARU is not communicating.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the rARUStatusSysTempUnits OID (Celsius or Fahrenheit).
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
Source file: Download powernet.mib · Publisher's file
Copy from Netdisco; File: apc/powernet.mib; 2.7 MiB
Vendor MIB copy from the Netdisco archive.
Related source files and packages:
- Netdisco archive revision metadata (not a manufacturer release date)File: repos/netdisco/netdisco-mibs/commits/master; 15,422 bytes
- Netdisco MIB distribution at the selected archive revision38.9 MiB
Source file: Download PowerNet-MIB · Publisher's file
Copy from Observium Community; File: apc/PowerNet-MIB; 2.8 MiB
Vendor MIB copy from the Observium Community archive.
Related source files and packages:
- Observium Community original distribution archivePublisher Last-Modified: Tue, 05 May 2026 13:47:48 GMT; 127.4 MiB
Source file: Download PowerNet-MIB · Publisher's file
Copy from LibreNMS; File: apc/PowerNet-MIB; 2.7 MiB
Vendor MIB copy from the LibreNMS archive.
Related source files and packages:
- LibreNMS original distribution archiveFile: librenms/librenms/tar.gz/…; 80.2 MiB
- Archive revision metadata: librenms/librenms (JSON)File: repos/librenms/librenms/commits/master; 36,945 bytes
Source file: Download PowerNet-MIB.mib
Publisher path: Mibs; 2.2 MiB
Alternative description: MIBdepot
The exhaust temperature in the lower plenum on 2nd generation ARUs.
NOTE: -1 will be returned if the ARU is not communicating.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the rARUStatusSysTempUnits OID (Celsius or Fahrenheit).
Source file: Download powernet410.mib.txt
File: apc/powernet410.mib.txt; 2.1 MiB
Source file: Download powernet401.mib.txt
File: apc/powernet401.mib.txt; 2.1 MiB
Source file: Download powernet395.mib.txt
File: apc/powernet395.mib.txt; 1.8 MiB
Source file: Download powernet388.mib.txt
File: apc/powernet388.mib.txt; 1.4 MiB
Source file: Download powernet387.mib.txt
File: apc/powernet387.mib.txt; 1.4 MiB
Information from MIBdepot
rARUStatusAruTemp3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"ARU temperature probe #3 reading.
The exhaust temperature in the lower plenum on 2nd generation ARUs.
NOTE: -1 will be returned if the ARU is not communicating.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
::= { rARUStatusEntry 7 }
Information from OID Repository
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
Information from Circitor
rARUStatusAruTemp3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"ARU temperature probe #3 reading.
The exhaust temperature in the lower plenum on 2nd generation ARUs.
NOTE: -1 will be returned if the ARU is not communicating.
Values are represented in whole number degrees.
Units are displayed in the scale shown in
the rARUStatusSysTempUnits OID (Celsius or Fahrenheit)."
::= { rARUStatusEntry 7 }
First Registration Authority (inferred from ancestor 1.3.6.1.4.1.318)
Siblings (13)
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.318.1.1.14.3.3.1.1 | rARUStatusAruIndex | 0 | 0 | The index to the ARU entry. |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.2 | rARUStatusAruName | 0 | 0 | The name of the ARU. |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.3 | rARUStatusAruRemoteSetpoint | 0 | 0 | This OID defines the desired base airflow of the ARU, or the speed of the ARU fans when the temperature override is inactive. See… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.4 | rARUStatusAruManualSetpoint | 0 | 0 | Manual operating setpoint of the ARU, which is set on the panel of the ARU. If the ARU doesn't have a manual , the OID will alway… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.5 | rARUStatusAruTemp1 | 0 | 0 | ARU temperature probe #1 reading. The summary exhaust temperature on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.6 | rARUStatusAruTemp2 | 0 | 0 | ARU temperature probe #2 reading. The exhaust temperature in the upper plenum on 2nd generation ARUs. NOTE: -1 will be returned i… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.8 | rARUStatusAruTempOvrdEnableDisable | 0 | 0 | This OID indicates whether the ARU remote temperature override is enabled or disabled. If this OID is a 1, the remote setting fo… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.9 | rARUStatusAruTempOvrdSetpoint | 0 | 0 | ARU remote temperature override setpoint setting. NOTE: -1 will be returned if the ARU is not communicating. Values are represent… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.10 | rARUStatusAruAlarmState | 0 | 0 | An ASCII string containing the 8 flags representing the current alarm state of the ARU. If the state of the ARU is unknown, this … |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.11 | rARUStatusAruCommStatus | 0 | 0 | The state of communications to the device. commNeverDiscovered(1) indicates there has never been communications with this device… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.12 | rARUStatusAruTempOvrdStatus | 0 | 0 | Specifies whether the ARU is increasing airflow because exhaust air temperature has exceeded the setting specified in the rARUCon… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.13 | rARUStatusAruMasterControl | 0 | 0 | This is the master on/off control for the ARU. |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.14 | rARUStatusAruTotalAirflow | 0 | 0 | The total airflow provided by the aru. Specified in cfm (cubic feet per minute). Can be converted to metric values using the con… |