Manual operating setpoint of the ARU, which is set on the
panel of the ARU. If the ARU doesn't have a manual ,
the OID will always return a value of aruRem (10).
NOTE: -1 will be returned if the ARU is not communicating.
Values are represented in whole number degrees or kW.
If the manual setpoint is set to Remote, or if the ARU doesn't
have a manual switch, this OID will return aruRem.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Manual operating setpoint of the ARU, which is set on the
panel of the ARU. If the ARU doesn't have a manual ,
the OID will always return a value of aruRem (10).
NOTE: -1 will be returned if the ARU is not communicating.
Values are represented in whole number degrees or kW.
If the manual setpoint is set to Remote, or if the ARU doesn't
have a manual switch, this OID will return aruRem.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
rARUStatusAruManualSetpoint OBJECT-TYPE SYNTAX INTEGER { aruOff (1), aru85F-29C (2), aru90F-32C (3), aru95F-35C (4), aru100F-38C (5), aru7kW (6), aru5kW (7), aru3kW (8), aru2kW (9), aruRem (10) } ACCESS read-only STATUS mandatory DESCRIPTION "Manual operating setpoint of the ARU, which is set on the panel of the ARU. If the ARU doesn't have a manual , the OID will always return a value of aruRem (10). NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees or kW. If the manual setpoint is set to Remote, or if the ARU doesn't have a manual switch, this OID will return aruRem." ::= { rARUStatusEntry 4 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
rARUStatusAruManualSetpoint OBJECT-TYPE SYNTAX INTEGER { aruOff (1), aru85F-29C (2), aru90F-32C (3), aru95F-35C (4), aru100F-38C (5), aru7kW (6), aru5kW (7), aru3kW (8), aru2kW (9), aruRem (10) } ACCESS read-only STATUS mandatory DESCRIPTION "Manual operating setpoint of the ARU, which is set on the panel of the ARU. If the ARU doesn't have a manual , the OID will always return a value of aruRem (10). NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees or kW. If the manual setpoint is set to Remote, or if the ARU doesn't have a manual switch, this OID will return aruRem." ::= { rARUStatusEntry 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.14.3.3.1.1 | rARUStatusAruIndex | 0 | 0 | The index to the ARU entry. |
1.3.6.1.4.1.318.1.1.14.3.3.1.2 | rARUStatusAruName | 0 | 0 | The name of the ARU. |
1.3.6.1.4.1.318.1.1.14.3.3.1.3 | rARUStatusAruRemoteSetpoint | 0 | 0 | This OID defines the desired base airflow of the ARU, or the speed of the ARU fans when the temperature override is inactive. See… |
1.3.6.1.4.1.318.1.1.14.3.3.1.5 | rARUStatusAruTemp1 | 0 | 0 | ARU temperature probe #1 reading. The summary exhaust temperature on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is… |
1.3.6.1.4.1.318.1.1.14.3.3.1.6 | rARUStatusAruTemp2 | 0 | 0 | ARU temperature probe #2 reading. The exhaust temperature in the upper plenum on 2nd generation ARUs. NOTE: -1 will be returned i… |
1.3.6.1.4.1.318.1.1.14.3.3.1.7 | rARUStatusAruTemp3 | 0 | 0 | ARU temperature probe #3 reading. The exhaust temperature in the lower plenum on 2nd generation ARUs. NOTE: -1 will be returned i… |
1.3.6.1.4.1.318.1.1.14.3.3.1.8 | rARUStatusAruTempOvrdEnableDisable | 0 | 0 | This OID indicates whether the ARU remote temperature override is enabled or disabled. If this OID is a 1, the remote setting fo… |
1.3.6.1.4.1.318.1.1.14.3.3.1.9 | rARUStatusAruTempOvrdSetpoint | 0 | 0 | ARU remote temperature override setpoint setting. NOTE: -1 will be returned if the ARU is not communicating. Values are represent… |
1.3.6.1.4.1.318.1.1.14.3.3.1.10 | rARUStatusAruAlarmState | 0 | 0 | An ASCII string containing the 8 flags representing the current alarm state of the ARU. If the state of the ARU is unknown, this … |
1.3.6.1.4.1.318.1.1.14.3.3.1.11 | rARUStatusAruCommStatus | 0 | 0 | The state of communications to the device. commNeverDiscovered(1) indicates there has never been communications with this device… |
1.3.6.1.4.1.318.1.1.14.3.3.1.12 | rARUStatusAruTempOvrdStatus | 0 | 0 | Specifies whether the ARU is increasing airflow because exhaust air temperature has exceeded the setting specified in the rARUCon… |
1.3.6.1.4.1.318.1.1.14.3.3.1.13 | rARUStatusAruMasterControl | 0 | 0 | This is the master on/off control for the ARU. |
1.3.6.1.4.1.318.1.1.14.3.3.1.14 | rARUStatusAruTotalAirflow | 0 | 0 | The total airflow provided by the aru. Specified in cfm (cubic feet per minute). Can be converted to metric values using the con… |