| 1.3.6.1.4.1.318.1.1.14.3.3.1.1 |
rARUStatusAruIndex | 0 | 0 |
The index to the ARU entry. |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.2 |
rARUStatusAruName | 0 | 0 |
The name of the ARU. |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.3 |
rARUStatusAruRemoteSetpoint | 0 | 0 |
This OID defines the desired base airflow of the ARU, or the speed of the ARU fans when the temperature override is inactive.
See… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.4 |
rARUStatusAruManualSetpoint | 0 | 0 |
Manual operating setpoint of the ARU, which is set on the panel of the ARU. If the ARU doesn't have a manual , the OID will alway… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.5 |
rARUStatusAruTemp1 | 0 | 0 |
ARU temperature probe #1 reading. The summary exhaust temperature on 2nd generation ARUs.
NOTE: -1 will be returned if the ARU is… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.6 |
rARUStatusAruTemp2 | 0 | 0 |
ARU temperature probe #2 reading. The exhaust temperature in the upper plenum on 2nd generation ARUs.
NOTE: -1 will be returned i… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.7 |
rARUStatusAruTemp3 | 0 | 0 |
ARU temperature probe #3 reading. The exhaust temperature in the lower plenum on 2nd generation ARUs.
NOTE: -1 will be returned i… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.8 |
rARUStatusAruTempOvrdEnableDisable | 0 | 0 |
This OID indicates whether the ARU remote temperature override is enabled or disabled. If this OID is a 1, the remote setting fo… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.9 |
rARUStatusAruTempOvrdSetpoint | 0 | 0 |
ARU remote temperature override setpoint setting.
NOTE: -1 will be returned if the ARU is not communicating.
Values are represent… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.10 |
rARUStatusAruAlarmState | 0 | 0 |
An ASCII string containing the 8 flags representing the current alarm state of the ARU. If the state of the ARU is unknown, this … |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.11 |
rARUStatusAruCommStatus | 0 | 0 |
The state of communications to the device. commNeverDiscovered(1) indicates there has never been communications with this device… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.12 |
rARUStatusAruTempOvrdStatus | 0 | 0 |
Specifies whether the ARU is increasing airflow because exhaust air temperature has exceeded the setting specified in the rARUCon… |
| 1.3.6.1.4.1.318.1.1.14.3.3.1.13 |
rARUStatusAruMasterControl | 0 | 0 |
This is the master on/off control for the ARU. |