There is no load detected on the output. This can be an indication
that the output is being powered by an external bypass source and has
inadvertently been left on external bypass. This warning is triggered
after a delay. The delay is specified by the object
'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output
current falls below a certain threshold specified by the object
'lgpPwrNoLoadWarningLimit'
Parsed from file LIEBERT_GP_COND.MIB.txt
Company: None
Module: LIEBERT-GP-CONDITIONS-MIB
There is no load detected on the output. This can be an indication
that the output is being powered by an external bypass source and has
inadvertently been left on external bypass. This warning is triggered
after a delay. The delay is specified by the object
'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output
current falls below a certain threshold specified by the object
'lgpPwrNoLoadWarningLimit'
Parsed from file LIEBERT-GP-CONDITIONS-MIB.mib
Module: LIEBERT-GP-CONDITIONS-MIB
Vendor: Emerson Computer PowerRoger Draper
Module: LIEBERT-GP-CONDITIONS-MIB
[Automatically extracted from oidview.com]
lgpConditionNoLoadDetectedWarning OBJECT-IDENTITY STATUS current DESCRIPTION "There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit'" ::= { lgpConditionsWellKnown 186 }
lgpConditionNoLoadDetectedWarning OBJECT-IDENTITY STATUS current DESCRIPTION "There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit'" ::= { lgpConditionsWellKnown 186 }
To many brothers! Only 100 nearest brothers are shown.
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
... | ||||
1.3.6.1.4.1.476.1.42.3.2.1.136 | lgpConditionUnitOn | 0 | 0 | The unit is on. |
1.3.6.1.4.1.476.1.42.3.2.1.137 | lgpConditionUnitOff | 0 | 0 | The unit is off. |
1.3.6.1.4.1.476.1.42.3.2.1.138 | lgpConditionSleepModeOff | 0 | 0 | The system sleep mode operation has been turned off. |
1.3.6.1.4.1.476.1.42.3.2.1.139 | lgpConditionPowerOn | 0 | 0 | The system power is on. |
1.3.6.1.4.1.476.1.42.3.2.1.140 | lgpConditionSystemOnStanby | 0 | 0 | The system is on standby. |
1.3.6.1.4.1.476.1.42.3.2.1.141 | lgpConditionPowerOff | 0 | 0 | The system power is off. |
1.3.6.1.4.1.476.1.42.3.2.1.142 | lgpConditionHighTemperatureGroup | 5 | 5 | lgpConditionHightemperatureGroup |
1.3.6.1.4.1.476.1.42.3.2.1.143 | lgpConditionLowTemperatureGroup | 2 | 2 | The system has detected a low temperature condition. This group contains various low temperature conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.144 | lgpConditionHighHumidityGroup | 1 | 1 | The system has detected a high humidity condition. This group contains various high humidity conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.145 | lgpConditionLowHumidityGroup | 1 | 1 | The system has detected a low humidity condition. This group contains various high humidity conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.146 | lgpConditionPeerNetworkNoMaster | 0 | 0 | The system is unable to communicate with the master on the peer to peer network. |
1.3.6.1.4.1.476.1.42.3.2.1.147 | lgpConditionNoOnOffPermissions | 0 | 0 | The system lacks the permissions to execute the on/off operation. |
1.3.6.1.4.1.476.1.42.3.2.1.148 | lgpConditionPeerNetworkFailure | 0 | 0 | The system has detected a communication failure on the peer to peer network. |
1.3.6.1.4.1.476.1.42.3.2.1.149 | lgpConditionUnitDisabled | 0 | 0 | The unit is disabled. |
1.3.6.1.4.1.476.1.42.3.2.1.150 | lgpConditionUnitShutdown | 0 | 0 | The system has shutdown. |
1.3.6.1.4.1.476.1.42.3.2.1.151 | lgpConditionPeerNetworkDiscovered | 0 | 0 | The system has established communications on the peer to peer network. |
1.3.6.1.4.1.476.1.42.3.2.1.152 | lgpConditionLossOfWaterFlow | 0 | 0 | The system has detected a loss of water flow condition. |
1.3.6.1.4.1.476.1.42.3.2.1.153 | lgpConditionCondensatePumpHighWater | 0 | 0 | The system has detected high water in the condensate pump. |
1.3.6.1.4.1.476.1.42.3.2.1.154 | lgpConditionGeneralAlarm | 0 | 0 | The system has detected a general alarm condition. |
1.3.6.1.4.1.476.1.42.3.2.1.155 | lgpConditionProductSpecific | 0 | 0 | The system has detected a product specific condition. This condition is not currently available via the agent card. |
1.3.6.1.4.1.476.1.42.3.2.1.156 | lgpConditionReheatLockout | 0 | 0 | The system has locked out the electrical reheat operation for a specified amount of time. |
1.3.6.1.4.1.476.1.42.3.2.1.157 | lgpConditionHumidifierLockout | 0 | 0 | The system has locked out the humidifier operation for a specified amount of time. |
1.3.6.1.4.1.476.1.42.3.2.1.158 | lgpConditionCompressorsLockout | 0 | 0 | The system has locked out compressor operation for a specified amount of time. |
1.3.6.1.4.1.476.1.42.3.2.1.159 | lgpConditionCallService | 0 | 0 | The system has detected a condition that requires a service representative be contacted. |
1.3.6.1.4.1.476.1.42.3.2.1.160 | lgpConditionLowMemoryGroup | 1 | 1 | This group contains various low memory conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.161 | lgpConditionMemoryFailureGroup | 2 | 2 | This group contains various memory device failure conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.162 | lgpConditionUnitCodeErrorGroup | 19 | 19 | This group contains various memory device failure conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.163 | lgpConditionHighExternalDewPoint | 0 | 0 | The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold. |
1.3.6.1.4.1.476.1.42.3.2.1.164 | lgpConditionHcbDisconnected | 0 | 0 | The system has detected the humidifier control board is disconnected or not installed. |
1.3.6.1.4.1.476.1.42.3.2.1.165 | lgpConditionBmsResetTimerExpired | 0 | 0 | The BMS fan speed control reset counter has timed out. |
1.3.6.1.4.1.476.1.42.3.2.1.166 | lgpConditionAgentFirmwareCorrupt | 0 | 0 | The firmware update to the agent card has failed and the firmware is now corrupt. |
1.3.6.1.4.1.476.1.42.3.2.1.175 | lgpConditionSystemAccessGroup | 2 | 2 | This group contains various system access conditions. An examples is an open access panel. |
1.3.6.1.4.1.476.1.42.3.2.1.176 | lgpConditionsDamperFailure | 1 | 1 | This group contains various damper failure conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.177 | lgpConditionRemoteShutdown | 0 | 0 | A remote shutdown occurred. |
1.3.6.1.4.1.476.1.42.3.2.1.178 | lgpConditionFireAlarm | 0 | 0 | Fire Alarm. |
1.3.6.1.4.1.476.1.42.3.2.1.179 | lgpConditionHeatersOverheated | 0 | 0 | Heaters Overheated. |
1.3.6.1.4.1.476.1.42.3.2.1.180 | lgpConditionCondenserFailureGroup | 2 | 2 | This group contains condenser failure conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.181 | lgpConditionHumidifierCyclinderWorn | 0 | 0 | The system has detected the humidifier cylinder is worn. |
1.3.6.1.4.1.476.1.42.3.2.1.182 | lgpConditionUnderCurrent | 2 | 2 | The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold … |
1.3.6.1.4.1.476.1.42.3.2.1.183 | lgpConditionHeatRejectorGroup | 2 | 2 | This group contains failure conditions for the heat rejection unit. |
1.3.6.1.4.1.476.1.42.3.2.1.184 | lgpConditionFreeCoolLockout | 0 | 0 | The free cooling capability has been disabled. |
1.3.6.1.4.1.476.1.42.3.2.1.185 | lgpConditionWaterLeakSensorFailure | 0 | 0 | The sensor used to detect water leaks is not connected or has failed. |
1.3.6.1.4.1.476.1.42.3.2.1.187 | lgpConditionFirmwareGroup | 1 | 1 | Grouping level for firmware related conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.188 | lgpConditionTestGroup | 1 | 1 | Objects in this group of conditions are related to testing or test events. This object is never active. |
1.3.6.1.4.1.476.1.42.3.2.1.190 | lgpConditionReceptacleBranchGroup | 2 | 2 | Grouping level for receptacle branch conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.192 | lgpConditionInputUnqualified | 0 | 0 | The input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-vol… |
1.3.6.1.4.1.476.1.42.3.2.1.193 | lgpConditionBypassUnavailable | 0 | 0 | This summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, B… |
1.3.6.1.4.1.476.1.42.3.2.1.194 | lgpConditionAutoTransferFailed | 0 | 0 | The system is failing to automatically transfer the load to the alternate source. |
1.3.6.1.4.1.476.1.42.3.2.1.195 | lgpConditionSBSUnavailable | 0 | 0 | A Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rec… |
1.3.6.1.4.1.476.1.42.3.2.1.196 | lgpConditionSBSOverload | 0 | 0 | On at least one phase of the static bypass switch (SBS), the power dissapation limit has been exceeded. |
1.3.6.1.4.1.476.1.42.3.2.1.197 | lgpConditionExcessPulseParallel | 0 | 0 | The system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a… |
1.3.6.1.4.1.476.1.42.3.2.1.198 | lgpConditionRemoteBypassSwitchOffExt | 0 | 0 | The static bypass switch is off due to the state of an external signal. |
1.3.6.1.4.1.476.1.42.3.2.1.199 | lgpConditionManTransferInhibited | 0 | 0 | Manual transfer from inverter to bypass is inhibited. Bypass is not qualified. |
1.3.6.1.4.1.476.1.42.3.2.1.200 | lgpConditionManReTransferInhibited | 0 | 0 | Manual retransfer from bypass to inverter is inhibited. |
1.3.6.1.4.1.476.1.42.3.2.1.201 | lgpConditionBatteryChargeError | 0 | 0 | The battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, b… |
1.3.6.1.4.1.476.1.42.3.2.1.202 | lgpConditionBatteryAutoTestInhibited | 0 | 0 | Automatic (scheduled) battery tests are inhibited. |
1.3.6.1.4.1.476.1.42.3.2.1.203 | lgpConditionBatteryChargeReducedExt | 0 | 0 | A reduced battery charging algorithm is being used due to an external signal. |
1.3.6.1.4.1.476.1.42.3.2.1.204 | lgpConditionBatteryCapacityLow | 0 | 0 | The battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery … |
1.3.6.1.4.1.476.1.42.3.2.1.205 | lgpConditionBatteryTempImbalance | 0 | 0 | The temperature difference between two batteries in the system exceeds the predefined threshold. |
1.3.6.1.4.1.476.1.42.3.2.1.206 | lgpConditionBatteryEqualize | 0 | 0 | The rectifier output voltage has been increased to equalize the battery voltage level. |
1.3.6.1.4.1.476.1.42.3.2.1.207 | lgpConditionBatteryChargeInhibitedExt | 0 | 0 | Battery charging is inhibited due to an external inhibit signal. |
1.3.6.1.4.1.476.1.42.3.2.1.208 | lgpConditionServiceExtBatteryMonitorGroup | 2 | 2 | This group contains battery monitor service conditions. |
1.3.6.1.4.1.476.1.42.3.2.1.209 | lgpConditionBatteryGroundFault | 0 | 0 | Battery system ground fault amperage exceeds the threshold. |
1.3.6.1.4.1.476.1.42.3.2.1.210 | lgpConditionBatteryLowShutdown | 0 | 0 | With the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit. |
1.3.6.1.4.1.476.1.42.3.2.1.211 | lgpConditionEmergencyPowerOffLocal | 0 | 0 | The system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system. |
1.3.6.1.4.1.476.1.42.3.2.1.212 | lgpConditionOutputLowPFLagging | 0 | 0 | The system has detected a lagging output power factor below the threshold, resulting in reduced load capacity. |
1.3.6.1.4.1.476.1.42.3.2.1.213 | lgpConditionOutputLowPFLeading | 0 | 0 | The system has detected a leading output power factor below the threshold, resulting in reduced load capacity. |
1.3.6.1.4.1.476.1.42.3.2.1.214 | lgpConditionOutputToLoadFault | 0 | 0 | The system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency. |
1.3.6.1.4.1.476.1.42.3.2.1.215 | lgpConditionInvRestartInhibitedExt | 0 | 0 | Restart of the inverter is inhibited by an external signal. |
1.3.6.1.4.1.476.1.42.3.2.1.216 | lgpConditionInverterShutdownOverload | 0 | 0 | The system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or tr… |
1.3.6.1.4.1.476.1.42.3.2.1.217 | lgpConditionInverterOffExt | 0 | 0 | The inverter is off due to the state of an external signal. |
1.3.6.1.4.1.476.1.42.3.2.1.218 | lgpConditionInputContactGroup | 16 | 16 | The system has detected an active input contact. |
1.3.6.1.4.1.476.1.42.3.2.1.219 | lgpConditionRectifierOperInhibited | 0 | 0 | None |
1.3.6.1.4.1.476.1.42.3.2.1.220 | lgpConditionBypassBackFeedBrkrOpen | 0 | 0 | The bypass backfeed breaker is in the open position. |
1.3.6.1.4.1.476.1.42.3.2.1.221 | lgpConditionAutoRestartInProgress | 0 | 0 | Auto restart is in progress. Becomes inactive when auto restart completes or fails. |
1.3.6.1.4.1.476.1.42.3.2.1.222 | lgpConditionAutoRestartInhibitedExt | 0 | 0 | Auto restart is inhibited due to an external signal. |
1.3.6.1.4.1.476.1.42.3.2.1.223 | lgpConditionAutoRestartFailed | 0 | 0 | Auto restart has failed. |
1.3.6.1.4.1.476.1.42.3.2.1.224 | lgpConditionInputOnGenerator | 0 | 0 | A generator is supplying the power to the system. |
1.3.6.1.4.1.476.1.42.3.2.1.225 | lgpConditionInputFilterCycleLock | 0 | 0 | The input filter disconnect has opened too many times within a given period of time. |
1.3.6.1.4.1.476.1.42.3.2.1.226 | lgpConditionServiceCodeActive | 0 | 0 | The system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this sta… |
1.3.6.1.4.1.476.1.42.3.2.1.227 | lgpConditionLoadBusSyncActive | 0 | 0 | Load Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS. |
1.3.6.1.4.1.476.1.42.3.2.1.228 | lgpConditionLoadBusSyncInhibited | 0 | 0 | The system has detected that conditions to perform Load Bus Sync Operation are not satisfied. |
1.3.6.1.4.1.476.1.42.3.2.1.229 | lgpConditionControlsResetRequired | 0 | 0 | A controls reset is required because one or more critical settings have changed. |
1.3.6.1.4.1.476.1.42.3.2.1.230 | lgpConditionEquipTempSensorFailed | 0 | 0 | A temperature sensor is reporting a value outside the bounds of a properly operating sensor. |
1.3.6.1.4.1.476.1.42.3.2.1.231 | lgpConditionInputCurrentImbalance | 0 | 0 | The current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper o… |
... |