Reference record for OID 1.3.6.1.4.1.476.1.42.3.4.4.1



parent
1.3.6.1.4.1.476.1.42.3.4.4 (lgpEnvConfig)
node code
1
node name
lgpEnvConfigReheatLockout
dot oid
1.3.6.1.4.1.476.1.42.3.4.4.1
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigReheatLockout(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigReheatLockout(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigReheatLockout(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigReheatLockout(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigReheatLockout(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigReheatLockout(1)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigReheatLockout
  • /iso/identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigReheatLockout
  • /iso/org/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigReheatLockout
  • /iso/org/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigReheatLockout
  • /iso/iso-identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigReheatLockout
  • /iso/iso-identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigReheatLockout
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/476/1/42/3/4/4/1

    Description by mibdepot

    If locked-out the reheats will not operate even if controller calls
    for its operation.

    Parsed from file LIEBERT_GP_ENV.MIB.txt
    Company: None
    Module: LIEBERT-GP-ENVIRONMENTAL-MIB

    Description by circitor

    If locked-out the reheats will not operate even if controller calls
    for its operation.

    Parsed from file LIEBERT-GP-ENVIRONMENTAL-MIB.mib
    Module: LIEBERT-GP-ENVIRONMENTAL-MIB

    Information by oid_info

    Vendor: Emerson Computer PowerRoger Draper
    Module: LIEBERT-GP-ENVIRONMENTAL-MIB

    [Automatically extracted from oidview.com]

    Information by mibdepot

    lgpEnvConfigReheatLockout OBJECT-TYPE SYNTAX INTEGER { lockedOut(1), notLockedOut(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "If locked-out the reheats will not operate even if controller calls for its operation." ::= { lgpEnvConfig 1 }

    Information by circitor

    lgpEnvConfigReheatLockout OBJECT-TYPE SYNTAX INTEGER { lockedOut(1), notLockedOut(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "If locked-out the reheats will not operate even if controller calls for its operation. " ::= { lgpEnvConfig 1 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.476)

    [email protected]

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.476.1.42.3.4.4.1.0 lgpEnvConfigReheatLockout 0 0 None

    Brothers (35)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.476.1.42.3.4.4.2 lgpEnvConfigHumLockout 1 1 If locked-out the humidifier will not operate even if controller
    calls for its operation.
    1.3.6.1.4.1.476.1.42.3.4.4.4 lgpEnvConfigRestartDelay 1 1 When utility power is disrupted, this is the delay interval to wait
    before restarting the system after the utility power is rest…
    1.3.6.1.4.1.476.1.42.3.4.4.7 lgpEnvConfigRemoteShutdown 1 1 When in the disabled state, the remote shutdown feature should
    be locked out. The enabled state is self-describing.
    1.3.6.1.4.1.476.1.42.3.4.4.8 lgpEnvConfigCoolingServiceInterval 1 1 The amount of time, in hours, between scheduled maintenance
    of the cooling system. When the cooling service timer reaches
    this v…
    1.3.6.1.4.1.476.1.42.3.4.4.9 lgpEnvConfigHumidifierServiceInterval 1 1 The amount of time, in hours, between scheduled maintenance
    of the humidifier. When the humidifier service timer reaches
    this va…
    1.3.6.1.4.1.476.1.42.3.4.4.10 lgpEnvConfigFilterServiceInterval 1 1 The amount of time, in hours, between scheduled maintenance
    of the system filter. When the filter service timer reaches this
    val…
    1.3.6.1.4.1.476.1.42.3.4.4.11 lgpEnvConfigSleepModeDeadbandRangeDegC 1 1 The allowable deviation above and below the temperature set point used
    to create a no control region, a deadband, where heating…
    1.3.6.1.4.1.476.1.42.3.4.4.12 lgpEnvConfigSleepModeDeadbandRangeDegF 1 1 The allowable deviation above and below the temperature set point used
    to create a no control region, a deadband, where heating…
    1.3.6.1.4.1.476.1.42.3.4.4.13 lgpEnvConfigSupplyTempLowLimitDegF 1 1 The minimum allowable supply temperature.
    1.3.6.1.4.1.476.1.42.3.4.4.14 lgpEnvConfigSupplyTempLowLimitDegC 1 1 The minimum allowable supply temperature.
    1.3.6.1.4.1.476.1.42.3.4.4.15 lgpEnvConfigTemperatureIntegTime 1 1 The value used as the integration factor in the proportional
    integral derivative (PID) temperature calculation.
    1.3.6.1.4.1.476.1.42.3.4.4.16 lgpEnvConfigLocalTemperatureUnit 1 1 The local temperature unit of the system.
    1.3.6.1.4.1.476.1.42.3.4.4.17 lgpEnvConfigSleepMode 1 1 The configured mode of the device's sleep function. If 'enabled',
    the device will sleep, or not operate, for each 'lgpEnvSleepD…
    1.3.6.1.4.1.476.1.42.3.4.4.18 lgpEnvConfigHumidityIntegTime 1 1 The value used as the integration factor in the proportional
    integral derivative (PID) humidity calculation.
    1.3.6.1.4.1.476.1.42.3.4.4.19 lgpEnvConfigFreecoolingDeltaDegF 1 1 The minimum temperature differential between the control
    temperature measurement and the coolant required to utilize
    Freecooling.
    1.3.6.1.4.1.476.1.42.3.4.4.20 lgpEnvConfigFreecoolingDeltaDegC 1 1 The minimum temperature differential between the control
    temperature measurement and the coolant required to utilize
    Freecooling.
    1.3.6.1.4.1.476.1.42.3.4.4.21 lgpEnvConfigSupplyTempLowLimit 1 1 The system configuration parameter to enable or disable the supply
    air low temperature limit.
    1.3.6.1.4.1.476.1.42.3.4.4.22 lgpEnvConfigSensorEventsStandard 1 1 The system configuration parameter to enable or disable the standard
    sensor events.
    1.3.6.1.4.1.476.1.42.3.4.4.23 lgpEnvConfigSensorEvents1 1 1 The system configuration parameter to enable or disable sensor 1 events.
    1.3.6.1.4.1.476.1.42.3.4.4.24 lgpEnvConfigSleepModeDeadbandRange 1 1 The system configuration parameter to enable or disable the use of
    the sleep interval deadband range in the sleep mode temperatu…
    1.3.6.1.4.1.476.1.42.3.4.4.25 lgpEnvConfigAutoConfiguration 1 1 The system configuration parameter to enable or disable the auto
    configuration feature. This feature configures temperature and…
    1.3.6.1.4.1.476.1.42.3.4.4.26 lgpEnvConfigDeltaGlycolType 1 1 The system configuration parameter that specifies how the system
    will determine if there is enough capacity to initiate free
    cool…
    1.3.6.1.4.1.476.1.42.3.4.4.27 lgpEnvConfigChillWaterControl 1 1 The system configuration parameter to enable or disable the minimum
    chill water temperature control.
    1.3.6.1.4.1.476.1.42.3.4.4.28 lgpEnvConfigInfaredFlushRate 1 1 The Infrared humidifier pan overfill rate. This parameter configures
    the amount of water that flows into the humidifier pan whe…
    1.3.6.1.4.1.476.1.42.3.4.4.29 lgpEnvConfigHumidityControl 1 1 The present configured state of the automatic humidity compensation
    algorithm.
    1.3.6.1.4.1.476.1.42.3.4.4.30 lgpEnvConfigCompressorLockout 1 1 The system as locked out the compressor(s). If locked-out, the
    compressor(s) will not operate even if the controller calls for …
    1.3.6.1.4.1.476.1.42.3.4.4.31 lgpEnvConfigReheatAndHumidifierLockout 1 1 The system as locked out the compressor(s). If locked-out, the
    electrical reheats and humidifier will not operate even if the
    co…
    1.3.6.1.4.1.476.1.42.3.4.4.32 lgpEnvOperationalTimeTable 1 7 A list of environmental operational time ranges for a given
    envionmental unit. The entries in this table may be duplicated from…
    1.3.6.1.4.1.476.1.42.3.4.4.33 lgpEnvConfigTempControlAlgorithm 1 1 Selects the algorithm for controlling temperature.
    1.3.6.1.4.1.476.1.42.3.4.4.34 lgpEnvConfigFanSpeedMode 1 1 Changes the function of the fanspeed output. If auto, then the fan
    speed is modulated. If manual, the fanspeed output follows
    l…
    1.3.6.1.4.1.476.1.42.3.4.4.35 lgpEnvConfigFanSpeedCapacity 1 1 Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to
    'manual'. Typical values range from 0 to 100% (actual valid ran…
    1.3.6.1.4.1.476.1.42.3.4.4.36 lgpEnvConfigBmsResetTimer 1 1 The current count-down time for a BMS to continue controlling the fan
    speed. If this value reaches 0, then the condition
    lgpCond…
    1.3.6.1.4.1.476.1.42.3.4.4.37 lgpEnvConfigDisableSensorOffsetDegC 1 1 If any of the enclosure temperature sensors
    (lgpEnvEnclosureTemperatureSensors) are outside the average reading by
    this amount, t…
    1.3.6.1.4.1.476.1.42.3.4.4.38 lgpEnvConfigDisableSensorOffsetDegF 1 1 If any of the enclosure temperature sensors
    (lgpEnvEnclosureTemperatureSensors) are outside the average reading by
    this amount, t…
    1.3.6.1.4.1.476.1.42.3.4.4.39 lgpEnvConfigCabinetSensorAlarms 1 1 Enable or Disable Cabinet Sensor Alarms.