Reference record for OID 1.3.6.1.4.1.476.1.42.3.4.4.37



parent
1.3.6.1.4.1.476.1.42.3.4.4 (lgpEnvConfig)
node code
37
node name
lgpEnvConfigDisableSensorOffsetDegC
dot oid
1.3.6.1.4.1.476.1.42.3.4.4.37
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigDisableSensorOffsetDegC(37)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigDisableSensorOffsetDegC(37)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigDisableSensorOffsetDegC(37)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigDisableSensorOffsetDegC(37)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigDisableSensorOffsetDegC(37)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpEnvironmental(4) lgpEnvConfig(4) lgpEnvConfigDisableSensorOffsetDegC(37)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigDisableSensorOffsetDegC
  • /iso/identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigDisableSensorOffsetDegC
  • /iso/org/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigDisableSensorOffsetDegC
  • /iso/org/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigDisableSensorOffsetDegC
  • /iso/iso-identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigDisableSensorOffsetDegC
  • /iso/iso-identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpEnvironmental/lgpEnvConfig/lgpEnvConfigDisableSensorOffsetDegC
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/476/1/42/3/4/4/37

    Description by mibdepot

    If any of the enclosure temperature sensors
    (lgpEnvEnclosureTemperatureSensors) are outside the average reading by
    this amount, that sensor's readings will not be used.

    Parsed from file LIEBERT_GP_ENV.MIB.txt
    Company: None
    Module: LIEBERT-GP-ENVIRONMENTAL-MIB

    Description by circitor

    If any of the enclosure temperature sensors
    (lgpEnvEnclosureTemperatureSensors) are outside the average reading by
    this amount, that sensor's readings will not be used

    Parsed from file LIEBERT-GP-ENVIRONMENTAL-MIB.mib
    Module: LIEBERT-GP-ENVIRONMENTAL-MIB

    Information by oid_info

    Vendor: Emerson Computer PowerRoger Draper
    Module: LIEBERT-GP-ENVIRONMENTAL-MIB

    [Automatically extracted from oidview.com]

    Information by mibdepot

    lgpEnvConfigDisableSensorOffsetDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used." ::= { lgpEnvConfig 37 }

    Information by circitor

    lgpEnvConfigDisableSensorOffsetDegC OBJECT-TYPE SYNTAX Integer32 UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used" ::= { lgpEnvConfig 37 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.476)

    [email protected]

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.476.1.42.3.4.4.37.0 lgpEnvConfigDisableSensorOffsetDegC 0 0 None

    Brothers (35)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.476.1.42.3.4.4.1 lgpEnvConfigReheatLockout 1 1 If locked-out the reheats will not operate even if controller calls
    for its operation.
    1.3.6.1.4.1.476.1.42.3.4.4.2 lgpEnvConfigHumLockout 1 1 If locked-out the humidifier will not operate even if controller
    calls for its operation.
    1.3.6.1.4.1.476.1.42.3.4.4.4 lgpEnvConfigRestartDelay 1 1 When utility power is disrupted, this is the delay interval to wait
    before restarting the system after the utility power is rest…
    1.3.6.1.4.1.476.1.42.3.4.4.7 lgpEnvConfigRemoteShutdown 1 1 When in the disabled state, the remote shutdown feature should
    be locked out. The enabled state is self-describing.
    1.3.6.1.4.1.476.1.42.3.4.4.8 lgpEnvConfigCoolingServiceInterval 1 1 The amount of time, in hours, between scheduled maintenance
    of the cooling system. When the cooling service timer reaches
    this v…
    1.3.6.1.4.1.476.1.42.3.4.4.9 lgpEnvConfigHumidifierServiceInterval 1 1 The amount of time, in hours, between scheduled maintenance
    of the humidifier. When the humidifier service timer reaches
    this va…
    1.3.6.1.4.1.476.1.42.3.4.4.10 lgpEnvConfigFilterServiceInterval 1 1 The amount of time, in hours, between scheduled maintenance
    of the system filter. When the filter service timer reaches this
    val…
    1.3.6.1.4.1.476.1.42.3.4.4.11 lgpEnvConfigSleepModeDeadbandRangeDegC 1 1 The allowable deviation above and below the temperature set point used
    to create a no control region, a deadband, where heating…
    1.3.6.1.4.1.476.1.42.3.4.4.12 lgpEnvConfigSleepModeDeadbandRangeDegF 1 1 The allowable deviation above and below the temperature set point used
    to create a no control region, a deadband, where heating…
    1.3.6.1.4.1.476.1.42.3.4.4.13 lgpEnvConfigSupplyTempLowLimitDegF 1 1 The minimum allowable supply temperature.
    1.3.6.1.4.1.476.1.42.3.4.4.14 lgpEnvConfigSupplyTempLowLimitDegC 1 1 The minimum allowable supply temperature.
    1.3.6.1.4.1.476.1.42.3.4.4.15 lgpEnvConfigTemperatureIntegTime 1 1 The value used as the integration factor in the proportional
    integral derivative (PID) temperature calculation.
    1.3.6.1.4.1.476.1.42.3.4.4.16 lgpEnvConfigLocalTemperatureUnit 1 1 The local temperature unit of the system.
    1.3.6.1.4.1.476.1.42.3.4.4.17 lgpEnvConfigSleepMode 1 1 The configured mode of the device's sleep function. If 'enabled',
    the device will sleep, or not operate, for each 'lgpEnvSleepD…
    1.3.6.1.4.1.476.1.42.3.4.4.18 lgpEnvConfigHumidityIntegTime 1 1 The value used as the integration factor in the proportional
    integral derivative (PID) humidity calculation.
    1.3.6.1.4.1.476.1.42.3.4.4.19 lgpEnvConfigFreecoolingDeltaDegF 1 1 The minimum temperature differential between the control
    temperature measurement and the coolant required to utilize
    Freecooling.
    1.3.6.1.4.1.476.1.42.3.4.4.20 lgpEnvConfigFreecoolingDeltaDegC 1 1 The minimum temperature differential between the control
    temperature measurement and the coolant required to utilize
    Freecooling.
    1.3.6.1.4.1.476.1.42.3.4.4.21 lgpEnvConfigSupplyTempLowLimit 1 1 The system configuration parameter to enable or disable the supply
    air low temperature limit.
    1.3.6.1.4.1.476.1.42.3.4.4.22 lgpEnvConfigSensorEventsStandard 1 1 The system configuration parameter to enable or disable the standard
    sensor events.
    1.3.6.1.4.1.476.1.42.3.4.4.23 lgpEnvConfigSensorEvents1 1 1 The system configuration parameter to enable or disable sensor 1 events.
    1.3.6.1.4.1.476.1.42.3.4.4.24 lgpEnvConfigSleepModeDeadbandRange 1 1 The system configuration parameter to enable or disable the use of
    the sleep interval deadband range in the sleep mode temperatu…
    1.3.6.1.4.1.476.1.42.3.4.4.25 lgpEnvConfigAutoConfiguration 1 1 The system configuration parameter to enable or disable the auto
    configuration feature. This feature configures temperature and…
    1.3.6.1.4.1.476.1.42.3.4.4.26 lgpEnvConfigDeltaGlycolType 1 1 The system configuration parameter that specifies how the system
    will determine if there is enough capacity to initiate free
    cool…
    1.3.6.1.4.1.476.1.42.3.4.4.27 lgpEnvConfigChillWaterControl 1 1 The system configuration parameter to enable or disable the minimum
    chill water temperature control.
    1.3.6.1.4.1.476.1.42.3.4.4.28 lgpEnvConfigInfaredFlushRate 1 1 The Infrared humidifier pan overfill rate. This parameter configures
    the amount of water that flows into the humidifier pan whe…
    1.3.6.1.4.1.476.1.42.3.4.4.29 lgpEnvConfigHumidityControl 1 1 The present configured state of the automatic humidity compensation
    algorithm.
    1.3.6.1.4.1.476.1.42.3.4.4.30 lgpEnvConfigCompressorLockout 1 1 The system as locked out the compressor(s). If locked-out, the
    compressor(s) will not operate even if the controller calls for …
    1.3.6.1.4.1.476.1.42.3.4.4.31 lgpEnvConfigReheatAndHumidifierLockout 1 1 The system as locked out the compressor(s). If locked-out, the
    electrical reheats and humidifier will not operate even if the
    co…
    1.3.6.1.4.1.476.1.42.3.4.4.32 lgpEnvOperationalTimeTable 1 7 A list of environmental operational time ranges for a given
    envionmental unit. The entries in this table may be duplicated from…
    1.3.6.1.4.1.476.1.42.3.4.4.33 lgpEnvConfigTempControlAlgorithm 1 1 Selects the algorithm for controlling temperature.
    1.3.6.1.4.1.476.1.42.3.4.4.34 lgpEnvConfigFanSpeedMode 1 1 Changes the function of the fanspeed output. If auto, then the fan
    speed is modulated. If manual, the fanspeed output follows
    l…
    1.3.6.1.4.1.476.1.42.3.4.4.35 lgpEnvConfigFanSpeedCapacity 1 1 Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to
    'manual'. Typical values range from 0 to 100% (actual valid ran…
    1.3.6.1.4.1.476.1.42.3.4.4.36 lgpEnvConfigBmsResetTimer 1 1 The current count-down time for a BMS to continue controlling the fan
    speed. If this value reaches 0, then the condition
    lgpCond…
    1.3.6.1.4.1.476.1.42.3.4.4.38 lgpEnvConfigDisableSensorOffsetDegF 1 1 If any of the enclosure temperature sensors
    (lgpEnvEnclosureTemperatureSensors) are outside the average reading by
    this amount, t…
    1.3.6.1.4.1.476.1.42.3.4.4.39 lgpEnvConfigCabinetSensorAlarms 1 1 Enable or Disable Cabinet Sensor Alarms.