A list of environmental operational time ranges for a given
environmental unit. The entries in this table may be duplicated from
values in the 'lgpEnvStatistics' group.
This table contains zero, one, or many rows, depending upon the number
of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available
in the table.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device.
Parsed from file LIEBERT_GP_ENV.MIB.txt
Company: None
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
A list of environmental operational time ranges for a given
envionmental unit. The entries in this table may be duplicated from
values in the 'lgpEnvStatistics' group.
This table contains zero, one, or many rows, depending upon the number
of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available
in the table.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device.
Parsed from file LIEBERT-GP-ENVIRONMENTAL-MIB.mib
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
Vendor: Emerson Computer PowerRoger Draper
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
[Automatically extracted from oidview.com]
lgpEnvOperationalTimeTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvOperationalTimeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpEnvConfig 32 }
lgpEnvOperationalTimeTable OBJECT-TYPE SYNTAX SEQUENCE OF LgpEnvOperationalTimeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A list of environmental operational time ranges for a given envionmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device." ::= { lgpEnvConfig 32 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.4.4.32.1 | lgpEnvOperationalTimeEntry | 6 | 6 | This entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.4.4.1 | lgpEnvConfigReheatLockout | 1 | 1 | If locked-out the reheats will not operate even if controller calls for its operation. |
1.3.6.1.4.1.476.1.42.3.4.4.2 | lgpEnvConfigHumLockout | 1 | 1 | If locked-out the humidifier will not operate even if controller calls for its operation. |
1.3.6.1.4.1.476.1.42.3.4.4.4 | lgpEnvConfigRestartDelay | 1 | 1 | When utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is rest… |
1.3.6.1.4.1.476.1.42.3.4.4.7 | lgpEnvConfigRemoteShutdown | 1 | 1 | When in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing. |
1.3.6.1.4.1.476.1.42.3.4.4.8 | lgpEnvConfigCoolingServiceInterval | 1 | 1 | The amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this v… |
1.3.6.1.4.1.476.1.42.3.4.4.9 | lgpEnvConfigHumidifierServiceInterval | 1 | 1 | The amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this va… |
1.3.6.1.4.1.476.1.42.3.4.4.10 | lgpEnvConfigFilterServiceInterval | 1 | 1 | The amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this val… |
1.3.6.1.4.1.476.1.42.3.4.4.11 | lgpEnvConfigSleepModeDeadbandRangeDegC | 1 | 1 | The allowable deviation above and below the temperature set point used to create a no control region, a deadband, where heating… |
1.3.6.1.4.1.476.1.42.3.4.4.12 | lgpEnvConfigSleepModeDeadbandRangeDegF | 1 | 1 | The allowable deviation above and below the temperature set point used to create a no control region, a deadband, where heating… |
1.3.6.1.4.1.476.1.42.3.4.4.13 | lgpEnvConfigSupplyTempLowLimitDegF | 1 | 1 | The minimum allowable supply temperature. |
1.3.6.1.4.1.476.1.42.3.4.4.14 | lgpEnvConfigSupplyTempLowLimitDegC | 1 | 1 | The minimum allowable supply temperature. |
1.3.6.1.4.1.476.1.42.3.4.4.15 | lgpEnvConfigTemperatureIntegTime | 1 | 1 | The value used as the integration factor in the proportional integral derivative (PID) temperature calculation. |
1.3.6.1.4.1.476.1.42.3.4.4.16 | lgpEnvConfigLocalTemperatureUnit | 1 | 1 | The local temperature unit of the system. |
1.3.6.1.4.1.476.1.42.3.4.4.17 | lgpEnvConfigSleepMode | 1 | 1 | The configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepD… |
1.3.6.1.4.1.476.1.42.3.4.4.18 | lgpEnvConfigHumidityIntegTime | 1 | 1 | The value used as the integration factor in the proportional integral derivative (PID) humidity calculation. |
1.3.6.1.4.1.476.1.42.3.4.4.19 | lgpEnvConfigFreecoolingDeltaDegF | 1 | 1 | The minimum temperature differential between the control temperature measurement and the coolant required to utilize Freecooling. |
1.3.6.1.4.1.476.1.42.3.4.4.20 | lgpEnvConfigFreecoolingDeltaDegC | 1 | 1 | The minimum temperature differential between the control temperature measurement and the coolant required to utilize Freecooling. |
1.3.6.1.4.1.476.1.42.3.4.4.21 | lgpEnvConfigSupplyTempLowLimit | 1 | 1 | The system configuration parameter to enable or disable the supply air low temperature limit. |
1.3.6.1.4.1.476.1.42.3.4.4.22 | lgpEnvConfigSensorEventsStandard | 1 | 1 | The system configuration parameter to enable or disable the standard sensor events. |
1.3.6.1.4.1.476.1.42.3.4.4.23 | lgpEnvConfigSensorEvents1 | 1 | 1 | The system configuration parameter to enable or disable sensor 1 events. |
1.3.6.1.4.1.476.1.42.3.4.4.24 | lgpEnvConfigSleepModeDeadbandRange | 1 | 1 | The system configuration parameter to enable or disable the use of the sleep interval deadband range in the sleep mode temperatu… |
1.3.6.1.4.1.476.1.42.3.4.4.25 | lgpEnvConfigAutoConfiguration | 1 | 1 | The system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and… |
1.3.6.1.4.1.476.1.42.3.4.4.26 | lgpEnvConfigDeltaGlycolType | 1 | 1 | The system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cool… |
1.3.6.1.4.1.476.1.42.3.4.4.27 | lgpEnvConfigChillWaterControl | 1 | 1 | The system configuration parameter to enable or disable the minimum chill water temperature control. |
1.3.6.1.4.1.476.1.42.3.4.4.28 | lgpEnvConfigInfaredFlushRate | 1 | 1 | The Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan whe… |
1.3.6.1.4.1.476.1.42.3.4.4.29 | lgpEnvConfigHumidityControl | 1 | 1 | The present configured state of the automatic humidity compensation algorithm. |
1.3.6.1.4.1.476.1.42.3.4.4.30 | lgpEnvConfigCompressorLockout | 1 | 1 | The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for … |
1.3.6.1.4.1.476.1.42.3.4.4.31 | lgpEnvConfigReheatAndHumidifierLockout | 1 | 1 | The system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the co… |
1.3.6.1.4.1.476.1.42.3.4.4.33 | lgpEnvConfigTempControlAlgorithm | 1 | 1 | Selects the algorithm for controlling temperature. |
1.3.6.1.4.1.476.1.42.3.4.4.34 | lgpEnvConfigFanSpeedMode | 1 | 1 | Changes the function of the fanspeed output. If auto, then the fan speed is modulated. If manual, the fanspeed output follows l… |
1.3.6.1.4.1.476.1.42.3.4.4.35 | lgpEnvConfigFanSpeedCapacity | 1 | 1 | Sets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ran… |
1.3.6.1.4.1.476.1.42.3.4.4.36 | lgpEnvConfigBmsResetTimer | 1 | 1 | The current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpCond… |
1.3.6.1.4.1.476.1.42.3.4.4.37 | lgpEnvConfigDisableSensorOffsetDegC | 1 | 1 | If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, t… |
1.3.6.1.4.1.476.1.42.3.4.4.38 | lgpEnvConfigDisableSensorOffsetDegF | 1 | 1 | If any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, t… |
1.3.6.1.4.1.476.1.42.3.4.4.39 | lgpEnvConfigCabinetSensorAlarms | 1 | 1 | Enable or Disable Cabinet Sensor Alarms. |