This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off.(*)
Parsed from file GE_PARALLELUPS.mib.txt
Company: ge
Module: GE_PARALLELUPS
Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
upsShutdownType_sixth OBJECT-TYPE SYNTAX Integer32 { output(1), system(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)" ::= { upsControl_sixth 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.8.1.0 | 0 | 0 | 0 | upsShutdownType_sixth |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.8.2 | upsShutdownAfterDelay_sixth | 1 | 1 | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShut… |
1.3.6.1.4.1.818.1.1.16.8.3 | upsStartupAfterDelay_sixth | 1 | 1 | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setti… |
1.3.6.1.4.1.818.1.1.16.8.4 | upsRebootWithDuration_sixth | 1 | 1 | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the valu… |
1.3.6.1.4.1.818.1.1.16.8.5 | upsAutoRestart_sixth | 1 | 1 | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as… |
1.3.6.1.4.1.818.1.1.16.8.6 | upsReceptaclesNum_sixth | 1 | 1 | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
1.3.6.1.4.1.818.1.1.16.8.7 | upsReceptacleTable_sixth | 1 | 3 | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. |
1.3.6.1.4.1.818.1.1.16.8.8 | upsUPSMode_sixth | 1 | 1 | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a… |
1.3.6.1.4.1.818.1.1.16.8.9 | upsRectifierOnOff_sixth | 1 | 1 | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to … |
1.3.6.1.4.1.818.1.1.16.8.10 | upsBatteryChargeMethod_sixth | 1 | 1 | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the nor… |
1.3.6.1.4.1.818.1.1.16.8.11 | upsInverterOnOff_sixth | 1 | 1 | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'o… |
1.3.6.1.4.1.818.1.1.16.8.12 | upsBypassOnOff_sixth | 1 | 1 | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' … |
1.3.6.1.4.1.818.1.1.16.8.13 | upsLoadSource_sixth | 1 | 1 | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this … |