Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored.(*)
Parsed from file GE_PARALLELUPS.mib.txt
Company: ge
Module: GE_PARALLELUPS
Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
upsRebootWithDuration_sixth OBJECT-TYPE SYNTAX Integer32 (-1..300) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)" ::= { upsControl_sixth 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.8.4.0 | 0 | 0 | 0 | upsRebootWithDuration_sixth |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.16.8.1 | upsShutdownType_sixth | 1 | 1 | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRe… |
1.3.6.1.4.1.818.1.1.16.8.2 | upsShutdownAfterDelay_sixth | 1 | 1 | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShut… |
1.3.6.1.4.1.818.1.1.16.8.3 | upsStartupAfterDelay_sixth | 1 | 1 | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setti… |
1.3.6.1.4.1.818.1.1.16.8.5 | upsAutoRestart_sixth | 1 | 1 | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as… |
1.3.6.1.4.1.818.1.1.16.8.6 | upsReceptaclesNum_sixth | 1 | 1 | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
1.3.6.1.4.1.818.1.1.16.8.7 | upsReceptacleTable_sixth | 1 | 3 | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. |
1.3.6.1.4.1.818.1.1.16.8.8 | upsUPSMode_sixth | 1 | 1 | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a… |
1.3.6.1.4.1.818.1.1.16.8.9 | upsRectifierOnOff_sixth | 1 | 1 | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to … |
1.3.6.1.4.1.818.1.1.16.8.10 | upsBatteryChargeMethod_sixth | 1 | 1 | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the nor… |
1.3.6.1.4.1.818.1.1.16.8.11 | upsInverterOnOff_sixth | 1 | 1 | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'o… |
1.3.6.1.4.1.818.1.1.16.8.12 | upsBypassOnOff_sixth | 1 | 1 | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' … |
1.3.6.1.4.1.818.1.1.16.8.13 | upsLoadSource_sixth | 1 | 1 | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this … |