Reference record for OID 1.3.6.1.4.1.318.1.1.10.1.2.2.1.8



parent
1.3.6.1.4.1.318.1.1.10.1.2.2.1 (emConfigProbesEntry)
node code
8
node name
emConfigProbeHighTempEnable
dot oid
1.3.6.1.4.1.318.1.1.10.1.2.2.1.8
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) environmentalMonitor(10) external(1) emConfig(2) emConfigProbesTable(2) emConfigProbesEntry(1) emConfigProbeHighTempEnable(8)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) environmentalMonitor(10) external(1) emConfig(2) emConfigProbesTable(2) emConfigProbesEntry(1) emConfigProbeHighTempEnable(8)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) environmentalMonitor(10) external(1) emConfig(2) emConfigProbesTable(2) emConfigProbesEntry(1) emConfigProbeHighTempEnable(8)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) environmentalMonitor(10) external(1) emConfig(2) emConfigProbesTable(2) emConfigProbesEntry(1) emConfigProbeHighTempEnable(8)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) environmentalMonitor(10) external(1) emConfig(2) emConfigProbesTable(2) emConfigProbesEntry(1) emConfigProbeHighTempEnable(8)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) environmentalMonitor(10) external(1) emConfig(2) emConfigProbesTable(2) emConfigProbesEntry(1) emConfigProbeHighTempEnable(8)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/environmentalMonitor/external/emConfig/emConfigProbesTable/emConfigProbesEntry/emConfigProbeHighTempEnable
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/environmentalMonitor/external/emConfig/emConfigProbesTable/emConfigProbesEntry/emConfigProbeHighTempEnable
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/environmentalMonitor/external/emConfig/emConfigProbesTable/emConfigProbesEntry/emConfigProbeHighTempEnable
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/environmentalMonitor/external/emConfig/emConfigProbesTable/emConfigProbesEntry/emConfigProbeHighTempEnable
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/environmentalMonitor/external/emConfig/emConfigProbesTable/emConfigProbesEntry/emConfigProbeHighTempEnable
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/environmentalMonitor/external/emConfig/emConfigProbesTable/emConfigProbesEntry/emConfigProbeHighTempEnable
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/10/1/2/2/1/8

    Description by mibdepot

    The high temperature alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alarm will be
    generated if this value is set to enabled(2) and
    the threshold has been violated.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by oid_info

    emConfigProbeHightempEnable
    View at oid-info.com

    Description by circitor

    The high temperature alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alarm will be
    generated if this value is set to enabled(2) and
    the threshold has been violated.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    emConfigProbeHighTempEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated." ::= { emConfigProbesEntry 8 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    emConfigProbeHighTempEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated." ::= { emConfigProbesEntry 8 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Brothers (21)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.1 emConfigProbeNumber 0 0 The index into an Environmental Monitor probe entry.
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.2 emConfigProbeName 0 0 A descriptive name of the probe set by the user,
    possibly denoting its location or purpose.
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.3 emConfigProbeHighTempThreshold 0 0 emConfigProbeHightempThreshold
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.4 emConfigProbeLowTempThreshold 0 0 The low temperature alarm threshold for the probe.
    Units are displayed in the scale selected in
    the 'emConfigProbeTempUnits' OID …
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.5 emConfigProbeTempUnits 0 0 The temperature scale used to display the temperature
    thresholds of the probe, Celsius(1) or Fahrenheit(2).
    This setting is based…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.6 emConfigProbeHighHumidThreshold 0 0 The high humidity alarm threshold for the probe in
    percent relative humidity.
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.7 emConfigProbeLowHumidThreshold 0 0 The low humidity alarm threshold for the probe in
    percent relative humidity.
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.9 emConfigProbeLowTempEnable 0 0 The low temperature alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alarm…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.10 emConfigProbeHighHumidEnable 0 0 The high humidity alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alarm w…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.11 emConfigProbeLowHumidEnable 0 0 The low humidity alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alarm wi…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.12 emConfigProbeMaxTempThreshold 0 0 The maximum temperature alarm threshold for the probe.
    Units are displayed in the scale selected in
    the 'emConfigProbeTempUnits' …
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.13 emConfigProbeMinTempThreshold 0 0 The minimum temperature alarm threshold for the probe.
    Units are displayed in the scale selected in
    the 'emConfigProbeTempUnits' …
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.14 emConfigProbeMaxHumidThreshold 0 0 The maximun humidity alarm threshold for the probe in
    percent relative humidity.
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.15 emConfigProbeMinHumidThreshold 0 0 The minimum humidity alarm threshold for the probe in
    percent relative humidity.
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.16 emConfigProbeMaxTempEnable 0 0 The maximum temperature alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The a…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.17 emConfigProbeMinTempEnable 0 0 The minimum temperature alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The a…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.18 emConfigProbeMaxHumidEnable 0 0 The maximum humidity alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alar…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.19 emConfigProbeMinHumidEnable 0 0 The minimum humidity alarm enable/disable for the
    probe. No alarm will be generated if this value
    is set to disabled(1). The alar…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.20 emConfigProbeTempHysteresis 0 0 The number of degrees beyond the temperature thresholds
    at which an active temperature alarm will be cleared.
    This configuration …
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.21 emConfigProbeHumidHysteresis 0 0 The number of percent RH points beyond the humidity
    thresholds at which an active humidity alarm will be
    cleared. This configurat…
    1.3.6.1.4.1.318.1.1.10.1.2.2.1.22 emConfigProbeLocation 0 0 A string describing the location of the probe.