The max temperature violation status of the probe
temperature reading. This OID will show a maxTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is greater than or equal to
the maximun temperature threshold value, the
'emConfigProbeMaxTempThreshold' OID, and the value of the
'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show
noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled,
this OID will show disabled(3).
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The max temperature violation status of the probe
temperature reading. This OID will show a maxTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is greater than or equal to
the maximun temperature threshold value, the
'emConfigProbeMaxTempThreshold' OID, and the value of the
'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show
noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled,
this OID will show disabled(3).
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
emStatusProbeMaxTempViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), maxTempViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal to the maximun temperature threshold value, the 'emConfigProbeMaxTempThreshold' OID, and the value of the 'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 11 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
emStatusProbeMaxTempViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), maxTempViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal to the maximun temperature threshold value, the 'emConfigProbeMaxTempThreshold' OID, and the value of the 'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 11 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.10.1.3.3.1.1 | emStatusProbeNumber | 0 | 0 | The index of the probe. |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.2 | emStatusProbeName | 0 | 0 | A descriptive name for the probe set by the user, possibly denoting its location or purpose. |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.3 | emStatusProbeStatus | 0 | 0 | The connected status of the probe, either disconnected(1) or connected(2). |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.4 | emStatusProbeCurrentTemp | 0 | 0 | The current temperature reading from the probe displayed in the units shown in the 'emStatusProbeTempUnits' OID (Celsius or Fahre… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.5 | emStatusProbeTempUnits | 0 | 0 | The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.6 | emStatusProbeCurrentHumid | 0 | 0 | The current humidity reading from the probe in percent relative humidity. |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.7 | emStatusProbeHighTempViolation | 0 | 0 | emStatusProbeHightempViolation |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.8 | emStatusProbeLowTempViolation | 0 | 0 | The high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current t… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.9 | emStatusProbeHighHumidViolation | 0 | 0 | The high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidi… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.10 | emStatusProbeLowHumidViolation | 0 | 0 | The low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.12 | emStatusProbeMinTempViolation | 0 | 0 | The minimum temperature violation status of the probe temperature reading. This OID will show a minTempViolation(2) if the curren… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.13 | emStatusProbeMaxHumidViolation | 0 | 0 | The maximum humidity violation status of the probe humidity reading. This OID will show a maxTempViolation(2) if the current humi… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.14 | emStatusProbeMinHumidViolation | 0 | 0 | The minimum humidity violation status of the probe humidity reading. This OID will show a minTempViolation(2) if the current humi… |