The high temperature violation status of the probe
temperature reading. This OID will show a lowTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is less than or equal to
the low temperature threshold value, the
'emConfigProbeLowTempThreshold' OID, and the value of the
'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show
noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled,
this OID will show disabled(3).
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The high temperature violation status of the probe
temperature reading. This OID will show a lowTempViolation(2)
if the current temperature reading shown in the
'emStatusProbeCurrentTemp' OID is less than or equal to
the low temperature threshold value, the
'emConfigProbeLowTempThreshold' OID, and the value of the
'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show
noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled,
this OID will show disabled(3).
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
emStatusProbeLowTempViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), lowTempViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to the low temperature threshold value, the 'emConfigProbeLowTempThreshold' OID, and the value of the 'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 8 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
emStatusProbeLowTempViolation OBJECT-TYPE SYNTAX INTEGER { noViolation(1), lowTempViolation(2), disabled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to the low temperature threshold value, the 'emConfigProbeLowTempThreshold' OID, and the value of the 'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled, this OID will show disabled(3)." ::= { emStatusProbesEntry 8 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.10.1.3.3.1.1 | emStatusProbeNumber | 0 | 0 | The index of the probe. |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.2 | emStatusProbeName | 0 | 0 | A descriptive name for the probe set by the user, possibly denoting its location or purpose. |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.3 | emStatusProbeStatus | 0 | 0 | The connected status of the probe, either disconnected(1) or connected(2). |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.4 | emStatusProbeCurrentTemp | 0 | 0 | The current temperature reading from the probe displayed in the units shown in the 'emStatusProbeTempUnits' OID (Celsius or Fahre… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.5 | emStatusProbeTempUnits | 0 | 0 | The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.6 | emStatusProbeCurrentHumid | 0 | 0 | The current humidity reading from the probe in percent relative humidity. |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.7 | emStatusProbeHighTempViolation | 0 | 0 | emStatusProbeHightempViolation |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.9 | emStatusProbeHighHumidViolation | 0 | 0 | The high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidi… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.10 | emStatusProbeLowHumidViolation | 0 | 0 | The low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.11 | emStatusProbeMaxTempViolation | 0 | 0 | The max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current te… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.12 | emStatusProbeMinTempViolation | 0 | 0 | The minimum temperature violation status of the probe temperature reading. This OID will show a minTempViolation(2) if the curren… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.13 | emStatusProbeMaxHumidViolation | 0 | 0 | The maximum humidity violation status of the probe humidity reading. This OID will show a maxTempViolation(2) if the current humi… |
1.3.6.1.4.1.318.1.1.10.1.3.3.1.14 | emStatusProbeMinHumidViolation | 0 | 0 | The minimum humidity violation status of the probe humidity reading. This OID will show a minTempViolation(2) if the current humi… |