Reference record for OID 1.3.6.1.4.1.318.1.1.6.6.2.1.1.7



parent
1.3.6.1.4.1.318.1.1.6.6.2.1.1 (sPDUOutletConfigMSPgsEntry)
node code
7
node name
sPDUOutletConfigMSPgsLowBattWarning
dot oid
1.3.6.1.4.1.318.1.1.6.6.2.1.1.7
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUOutletConfigMSP(6) sPDUOutletConfigMSPgs(2) sPDUOutletConfigMSPgsTable(1) sPDUOutletConfigMSPgsEntry(1) sPDUOutletConfigMSPgsLowBattWarning(7)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUOutletConfigMSP(6) sPDUOutletConfigMSPgs(2) sPDUOutletConfigMSPgsTable(1) sPDUOutletConfigMSPgsEntry(1) sPDUOutletConfigMSPgsLowBattWarning(7)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUOutletConfigMSP(6) sPDUOutletConfigMSPgs(2) sPDUOutletConfigMSPgsTable(1) sPDUOutletConfigMSPgsEntry(1) sPDUOutletConfigMSPgsLowBattWarning(7)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUOutletConfigMSP(6) sPDUOutletConfigMSPgs(2) sPDUOutletConfigMSPgsTable(1) sPDUOutletConfigMSPgsEntry(1) sPDUOutletConfigMSPgsLowBattWarning(7)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUOutletConfigMSP(6) sPDUOutletConfigMSPgs(2) sPDUOutletConfigMSPgsTable(1) sPDUOutletConfigMSPgsEntry(1) sPDUOutletConfigMSPgsLowBattWarning(7)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUOutletConfigMSP(6) sPDUOutletConfigMSPgs(2) sPDUOutletConfigMSPgsTable(1) sPDUOutletConfigMSPgsEntry(1) sPDUOutletConfigMSPgsLowBattWarning(7)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/masterswitchMSP/sPDUOutletConfigMSP/sPDUOutletConfigMSPgs/sPDUOutletConfigMSPgsTable/sPDUOutletConfigMSPgsEntry/sPDUOutletConfigMSPgsLowBattWarning
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/masterswitchMSP/sPDUOutletConfigMSP/sPDUOutletConfigMSPgs/sPDUOutletConfigMSPgsTable/sPDUOutletConfigMSPgsEntry/sPDUOutletConfigMSPgsLowBattWarning
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/masterswitchMSP/sPDUOutletConfigMSP/sPDUOutletConfigMSPgs/sPDUOutletConfigMSPgsTable/sPDUOutletConfigMSPgsEntry/sPDUOutletConfigMSPgsLowBattWarning
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/masterswitchMSP/sPDUOutletConfigMSP/sPDUOutletConfigMSPgs/sPDUOutletConfigMSPgsTable/sPDUOutletConfigMSPgsEntry/sPDUOutletConfigMSPgsLowBattWarning
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/masterswitchMSP/sPDUOutletConfigMSP/sPDUOutletConfigMSPgs/sPDUOutletConfigMSPgsTable/sPDUOutletConfigMSPgsEntry/sPDUOutletConfigMSPgsLowBattWarning
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/masterswitchMSP/sPDUOutletConfigMSP/sPDUOutletConfigMSPgs/sPDUOutletConfigMSPgsTable/sPDUOutletConfigMSPgsEntry/sPDUOutletConfigMSPgsLowBattWarning
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/6/6/2/1/1/7

    Description by mibdepot

    The amount of delay, in 6 second intervals, between
    when the UPS goes on battery and the power down sequence for
    the outlet is initiated.

    Allowed values are:

    -2 - Never initiate the power down sequence on low battery warning.
    -1 - Initiate power down sequence based on remaining runtime.
    1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
    0 indicates to immediately initiate power down sequence on low
    battery warning.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    The amount of delay, in 6 second intervals, between
    when the UPS goes on battery and the power down sequence for
    the outlet is initiated.

    Allowed values are:

    -2 - Never initiate the power down sequence on low battery warning.
    -1 - Initiate power down sequence based on remaining runtime.
    1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
    0 indicates to immediately initiate power down sequence on low
    battery warning.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    sPDUOutletConfigMSPgsLowBattWarning OBJECT-TYPE SYNTAX INTEGER (-2..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in 6 second intervals, between when the UPS goes on battery and the power down sequence for the outlet is initiated. Allowed values are: -2 - Never initiate the power down sequence on low battery warning. -1 - Initiate power down sequence based on remaining runtime. 1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs). 0 indicates to immediately initiate power down sequence on low battery warning." ::= { sPDUOutletConfigMSPgsEntry 7 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    sPDUOutletConfigMSPgsLowBattWarning OBJECT-TYPE SYNTAX INTEGER (-2..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in 6 second intervals, between when the UPS goes on battery and the power down sequence for the outlet is initiated. Allowed values are: -2 - Never initiate the power down sequence on low battery warning. -1 - Initiate power down sequence based on remaining runtime. 1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs). 0 indicates to immediately initiate power down sequence on low battery warning." ::= { sPDUOutletConfigMSPgsEntry 7 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Brothers (12)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.1 sPDUOutletConfigMSPgsIndex 0 0 The index to the MasterSwitch plus.
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.2 sPDUOutletConfigMSPgsName 0 0 The name of the MasterSwitch plus. The maximum
    value is 23 characters. The name is set by
    using the sPDUMasterConfigMSPName OID.
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.3 sPDUOutletConfigMSPgsOutletIndex 0 0 The index to the outlet entry.
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.4 sPDUOutletConfigMSPgsOutletName 0 0 The name of the outlet. The maximum size is
    23 characters. The name is set by using the
    sPDUOutletConfigMSPallOutletName OID.
    This…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.5 sPDUOutletConfigMSPgsOutletCtrlMode 0 0 The Control Mode of the outlet.
    This OID is provided for informational purposes only.
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.6 sPDUOutletConfigMSPgsDeviceConfirm 0 0 Setting this OID to deviceConfirmNo (1) cause the outlet to
    NOT wait for device confirmation while performing graceful
    operations…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.8 sPDUOutletConfigMSPgsLowBattMult 0 0 Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is
    set to -1 (On Runtime Remaining).

    Allows you to set the value to s…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.9 sPDUOutletConfigMSPgsRestartDelay 0 0 The amount of delay, in 6 minute intervals, between
    when the outlet is turned off and the outlet is turned back on
    when performin…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.10 sPDUOutletConfigMSPgsPowerOnDelay 0 0 The amount of delay, in seconds, between the UPS entering
    normal (on-line) state and the outlet being powered on.

    Allowed values…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.11 sPDUOutletConfigMSPgsPowerOffDelay 0 0 The amount of delay, in seconds, between when the server
    shuts down and the outlet is powered off.

    Allowed values are:

    0 - 9999 s…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.12 sPDUOutletConfigMSPgsBattCapThresh 0 0 The minimum battery capacity, as a percent (0-100%), required
    of the UPS before an outlet will be allowed to power on.

    Allowed v…
    1.3.6.1.4.1.318.1.1.6.6.2.1.1.13 sPDUOutletConfigMSPgsRebootDuration 0 0 The amount of delay, in seconds, from outlet off until
    outlet on during a reboot.

    Allowed values are:

    0 - 9999 seconds (0 - 2 hrs…