The amount of delay, in 6 minute intervals, between
when the outlet is turned off and the outlet is turned back on
when performing a Graceful Shutdown.
Allowed values are:
-1 - Never turn outlet back on after a Graceful shutdown.
0 - 9999 six minute intervals (0 - 999hrs, 54 mins).
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The amount of delay, in 6 minute intervals, between
when the outlet is turned off and the outlet is turned back on
when performing a Graceful Shutdown.
Allowed values are:
-1 - Never turn outlet back on after a Graceful shutdown.
0 - 9999 six minute intervals (0 - 999hrs, 54 mins).
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
sPDUOutletConfigMSPgsRestartDelay OBJECT-TYPE SYNTAX INTEGER (-1..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in 6 minute intervals, between when the outlet is turned off and the outlet is turned back on when performing a Graceful Shutdown. Allowed values are: -1 - Never turn outlet back on after a Graceful shutdown. 0 - 9999 six minute intervals (0 - 999hrs, 54 mins)." ::= { sPDUOutletConfigMSPgsEntry 9 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
sPDUOutletConfigMSPgsRestartDelay OBJECT-TYPE SYNTAX INTEGER (-1..9999) ACCESS read-write STATUS mandatory DESCRIPTION " The amount of delay, in 6 minute intervals, between when the outlet is turned off and the outlet is turned back on when performing a Graceful Shutdown. Allowed values are: -1 - Never turn outlet back on after a Graceful shutdown. 0 - 9999 six minute intervals (0 - 999hrs, 54 mins)." ::= { sPDUOutletConfigMSPgsEntry 9 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.6.6.2.1.1.1 | sPDUOutletConfigMSPgsIndex | 0 | 0 | The index to the MasterSwitch plus. |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.2 | sPDUOutletConfigMSPgsName | 0 | 0 | The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.3 | sPDUOutletConfigMSPgsOutletIndex | 0 | 0 | The index to the outlet entry. |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.4 | sPDUOutletConfigMSPgsOutletName | 0 | 0 | The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.5 | sPDUOutletConfigMSPgsOutletCtrlMode | 0 | 0 | The Control Mode of the outlet. This OID is provided for informational purposes only. |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.6 | sPDUOutletConfigMSPgsDeviceConfirm | 0 | 0 | Setting this OID to deviceConfirmNo (1) cause the outlet to NOT wait for device confirmation while performing graceful operations… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.7 | sPDUOutletConfigMSPgsLowBattWarning | 0 | 0 | The amount of delay, in 6 second intervals, between when the UPS goes on battery and the power down sequence for the outlet is in… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.8 | sPDUOutletConfigMSPgsLowBattMult | 0 | 0 | Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is set to -1 (On Runtime Remaining). Allows you to set the value to s… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.10 | sPDUOutletConfigMSPgsPowerOnDelay | 0 | 0 | The amount of delay, in seconds, between the UPS entering normal (on-line) state and the outlet being powered on. Allowed values… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.11 | sPDUOutletConfigMSPgsPowerOffDelay | 0 | 0 | The amount of delay, in seconds, between when the server shuts down and the outlet is powered off. Allowed values are: 0 - 9999 s… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.12 | sPDUOutletConfigMSPgsBattCapThresh | 0 | 0 | The minimum battery capacity, as a percent (0-100%), required of the UPS before an outlet will be allowed to power on. Allowed v… |
1.3.6.1.4.1.318.1.1.6.6.2.1.1.13 | sPDUOutletConfigMSPgsRebootDuration | 0 | 0 | The amount of delay, in seconds, from outlet off until outlet on during a reboot. Allowed values are: 0 - 9999 seconds (0 - 2 hrs… |