The number of seconds an alarm for this input must
be present before annunication. The range of this
setting is 0..600.
This variable is stored in non-volatile memory.
Parsed from file Falconmib.txt
Company: None
Module: RLE-FALCON-MIB
The number of seconds an alarm for this input must
be present before annunication. The range of this
setting is 0..600.
This variable is stored in non-volatile memory.
Parsed from file RLE-FALCON-MIB.mib
Module: RLE-FALCON-MIB
Vendor: Raymond and Lae Engineering, Inc.
Module: RLE-FALCON-MIB
[Automatically extracted from oidview.com]
FalconInput8Delay OBJECT-TYPE SYNTAX INTEGER (0..600) ACCESS read-write STATUS mandatory DESCRIPTION "The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory." ::= { FalconInput8 10 }
falconInput8Delay OBJECT-TYPE SYNTAX INTEGER (0..600) ACCESS read-write STATUS mandatory DESCRIPTION "The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory." ::= { falconInput8 10 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.8.10.0 | 0 | 0 | 0 | FalconInput8LowLimit2 |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.8.1 | FalconInput8State | 1 | 1 | The state of use of Input Number 8. When a sensor is connected to Input 8 set State to installed(2) to indicate that the value of… |
1.3.6.1.4.1.3184.1.1.1.3.8.2 | FalconInput8Reading | 1 | 1 | The reading for sensor 8. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
1.3.6.1.4.1.3184.1.1.1.3.8.3 | FalconInput8Gain | 1 | 1 | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 8 to… |
1.3.6.1.4.1.3184.1.1.1.3.8.4 | FalconInput8Offset | 1 | 1 | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 8 to … |
1.3.6.1.4.1.3184.1.1.1.3.8.5 | FalconInput8Label | 1 | 1 | A user-defined text string associated with Input Number 8. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.8.6 | FalconInput8UOM | 1 | 1 | A user-defined text string associated with Input Number 8. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.8.7 | FalconInput8HighLimit2 | 1 | 1 | When input 8 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 8. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.8.8 | FalconInput8HighLimit | 1 | 1 | When input 8 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 8. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.8.9 | FalconInput8LowLimit, FalconInput8RlyControl | 1 | 1 | When input 8 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 8. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.8.11 | FalconInput8Hysteresis | 1 | 1 | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will cle… |