rPDU2Group OBJECT IDENTIFIER ::= { rPDU2 11 }
rPDU2Group OBJECT IDENTIFIER ::= { rPDU2 11 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.26.11.1 | rPDU2GroupNumberOfDevices | 0 | 0 | Getting this OID will return the number of Rack PDU devices contributing to the group power and energy values. |
1.3.6.1.4.1.318.1.1.26.11.2 | rPDU2GroupTotalPower | 0 | 0 | Getting this OID will return the total power consumption of the Rack PDU group devices in hundredths of kilowatts. |
1.3.6.1.4.1.318.1.1.26.11.3 | rPDU2GroupTotalEnergy | 0 | 0 | Getting this OID will return the total energy consumption of the Rack PDU group devices in tenths of kilowatt-hours. To reset th… |
1.3.6.1.4.1.318.1.1.26.11.4 | rPDU2GroupEnergyReset | 0 | 0 | Setting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU group to be reset to zero.… |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.26.1 | rPDU2IdentTableSize | 1 | 1 | The total number of Rack PDUs |
1.3.6.1.4.1.318.1.1.26.2 | rPDU2IdentTable | 1 | 11 | A table of Rack PDU identification data |
1.3.6.1.4.1.318.1.1.26.3 | rPDU2DeviceTableSize | 1 | 1 | The total number of Rack PDUs |
1.3.6.1.4.1.318.1.1.26.4 | rPDU2Device | 4 | 55 | None |
1.3.6.1.4.1.318.1.1.26.5 | rPDU2PhaseTableSize | 1 | 1 | The number of connected Rack PDU phases |
1.3.6.1.4.1.318.1.1.26.6 | rPDU2Phase | 3 | 29 | None |
1.3.6.1.4.1.318.1.1.26.7 | rPDU2BankTableSize | 1 | 1 | The number of connected Rack PDU banks |
1.3.6.1.4.1.318.1.1.26.8 | rPDU2Bank | 3 | 26 | None |
1.3.6.1.4.1.318.1.1.26.9 | rPDU2Outlet | 4 | 68 | None |
1.3.6.1.4.1.318.1.1.26.10 | rPDU2Sensor | 4 | 53 | None |
1.3.6.1.4.1.318.1.1.26.12 | rPDU2PhaseToPhaseStatusTableSize | 0 | 0 | The number of connected Rack PDU banks |
1.3.6.1.4.1.318.1.1.26.13 | rPDU2PhaseToPhase | 1 | 7 | None |