Reference record for OID 1.3.6.1.4.1.5528.30.10.40


parent
1.3.6.1.4.1.5528.30.10 (netBotz-prd-bot)
node code
40
node name
netBotz-prd-bot-amps3-enabled
dot oid
1.3.6.1.4.1.5528.30.10.40
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) netBotz(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) netBotzAPC(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • ...skipped...
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) netBotz(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) netBotzAPC(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) netBotz(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) netBotzAPC(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • ...skipped...
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) netBotz(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) netBotzAPC(5528) netBotz-products(30) netBotz-prd-bot(10) netBotz-prd-bot-amps3-enabled(40)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/netBotz/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • /iso/identified-organization/dod/internet/private/enterprise/netBotzAPC/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • ...skipped...
  • /iso/org/dod/internet/private/enterprise/netBotz/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • /iso/org/dod/internet/private/enterprise/netBotzAPC/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • /iso/org/dod/internet/private/enterprises/netBotz/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • /iso/org/dod/internet/private/enterprises/netBotzAPC/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • ...skipped...
  • /iso/iso-identified-organization/dod/internet/private/enterprises/netBotz/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • /iso/iso-identified-organization/dod/internet/private/enterprises/netBotzAPC/netBotz-products/netBotz-prd-bot/netBotz-prd-bot-amps3-enabled
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/5528/30/10/40

    Description by mibdepot

    Amperage[3] probe alarm enabled(1) or disabled(0).

    Parsed from file netbotz2.mib.txt
    Company: None
    Module: NETBOTZ-MIB

    Description by circitor

    Amperage[3] probe alarm enabled(1) or disabled(0).

    Parsed from file NETBOTZ-MIB.mib
    Module: NETBOTZ-MIB

    Information by oid_info

    Vendor: NetBotz
    Module: NETBOTZ-PRD-BOT-MIB

    [Automatically extracted from oidview.com]

    Information by mibdepot

    netBotz-prd-bot-amps3-enabled OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Amperage[3] probe alarm enabled(1) or disabled(0)." REFERENCE "NetBotz|Amperage[3] Probe Enabled" ::= { netBotz-prd-bot 40 }

    Information by circitor

    netBotz-prd-bot-amps3-enabled OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Amperage[3] probe alarm enabled(1) or disabled(0)." REFERENCE "NetBotz|Amperage[3] Probe Enabled" ::= { netBotz-prd-bot 40 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.5528)

    Fowler John

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.5528.30.10.40.0 netBotz-prd-bot-amps3-enabled 0 0 None

    Brothers (154)

    To many brothers! Only 100 nearest brothers are shown.

    OIDNameSub childrenSub Nodes TotalDescription
    ...
    1.3.6.1.4.1.5528.30.10.1 netBotz-prd-bot-temp 1 1 The reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.2 netBotz-prd-bot-humidity 1 1 The reading of the humidity probe, in percent.
    1.3.6.1.4.1.5528.30.10.3 netBotz-prd-bot-airflow 1 1 The reading of the airflow probe. Each unit represents approximately 40 feet/minute or
    13 meters/minute of airflow velocity.
    1.3.6.1.4.1.5528.30.10.4 netBotz-prd-bot-audio 1 1 The reading of the audio alarm probe on/off.
    1.3.6.1.4.1.5528.30.10.5 netBotz-prd-bot-doorajar 1 1 The reading of the door switch probe open(1) or closed(0).
    1.3.6.1.4.1.5528.30.10.6 netBotz-prd-bot-temp-min 1 1 The temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.7 netBotz-prd-bot-temp-max 1 1 The temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.8 netBotz-prd-bot-humidity-min 1 1 The humidity probe minimum, from 10 to 90 percent.
    1.3.6.1.4.1.5528.30.10.9 netBotz-prd-bot-humidity-max 1 1 The humidity probe maximum, from 10 to 90 percent.
    1.3.6.1.4.1.5528.30.10.10 netBotz-prd-bot-airflow-mins 1 1 Minutes without airflow before alarm set.
    1.3.6.1.4.1.5528.30.10.11 netBotz-prd-bot-audio-secs 1 1 Seconds of alarm audio before alarm set.
    1.3.6.1.4.1.5528.30.10.12 netBotz-prd-bot-temp-enabled 1 1 Temperature probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.13 netBotz-prd-bot-hum-enabled 1 1 Humidity probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.14 netBotz-prd-bot-air-enabled 1 1 Airflow probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.15 netBotz-prd-bot-audio-enabled 1 1 Audio probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.16 netBotz-prd-bot-switch-state 1 1 Switch state setting. The state controls which
    condition of the door switch indicates an alarm.
    If set to 0, alarm is set when th…
    1.3.6.1.4.1.5528.30.10.17 netBotz-prd-bot-switch-enabled 1 1 Door switch enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.18 netBotz-prd-bot-audio-level 1 1 Audio level setting. This is the relative audio level, from 0-11,
    above which an alarm will be sent.
    1.3.6.1.4.1.5528.30.10.19 netBotz-prd-bot-doorpic-delay 1 1 Number of seconds between door alert and first picture.
    1.3.6.1.4.1.5528.30.10.20 netBotz-prd-bot-trap-index 1 1 The crawler ID of the last trap.
    1.3.6.1.4.1.5528.30.10.21 netBotz-prd-bot-trap-address 1 1 The IP address of the last trap.
    1.3.6.1.4.1.5528.30.10.22 netBotz-prd-bot-trap-oid 1 1 The object id of the last trap.
    1.3.6.1.4.1.5528.30.10.23 netBotz-prd-bot-trap-value 1 1 The value of the last object trap.
    1.3.6.1.4.1.5528.30.10.24 netBotz-prd-bot-trap-date 1 1 The date and time of a specific trap. This field
    contains the number of seconds elapsed since
    midnight (00:00:00), January 1, 1970
    1.3.6.1.4.1.5528.30.10.26 netBotz-prd-bot-refresh 1 1 Rate of web page refresh, in seconds. This must be greater than 5 seconds.
    1.3.6.1.4.1.5528.30.10.27 netBotz-prd-bot-airflow-level 1 1 Airflow alert level. This is the relative level of airflow below which
    an alarm will be sent. The range is 1-11. Each unit is…
    1.3.6.1.4.1.5528.30.10.28 netBotz-prd-bot-doorpic-count 1 1 Number of pictures to take when door activated.
    These pictures will be sent as attachments to the door alert e-mail.
    The range is…
    1.3.6.1.4.1.5528.30.10.29 netBotz-prd-bot-amps1 1 1 The reading of the first amperage probe, in milliamps.
    1.3.6.1.4.1.5528.30.10.30 netBotz-prd-bot-amps1-enabled 1 1 Amperage[1] probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.31 netBotz-prd-bot-amps1-min 1 1 The amperage[1] probe minimum, from 0 to 30000 milliamps.
    1.3.6.1.4.1.5528.30.10.32 netBotz-prd-bot-amps1-max 1 1 The amperage[1] probe maximum, from 0 to 30000 milliamps.
    1.3.6.1.4.1.5528.30.10.34 netBotz-prd-bot-amps2 1 1 The reading of the second amperage probe, in milliamps.
    1.3.6.1.4.1.5528.30.10.35 netBotz-prd-bot-amps2-enabled 1 1 Amperage[2] probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.36 netBotz-prd-bot-amps2-min 1 1 The amperage[2] probe minimum, from 0 to 30000 milliamps.
    1.3.6.1.4.1.5528.30.10.37 netBotz-prd-bot-amps2-max 1 1 The amperage[2] probe maximum, from 0 to 30000 milliamps.
    1.3.6.1.4.1.5528.30.10.39 netBotz-prd-bot-amps3 1 1 The reading of the third amperage probe, in milliamps.
    1.3.6.1.4.1.5528.30.10.41 netBotz-prd-bot-amps3-min 1 1 The amperage[3] probe minimum, from 0 to 30000 milliamps.
    1.3.6.1.4.1.5528.30.10.42 netBotz-prd-bot-amps3-max 1 1 The amperage[3] probe maximum, from 0 to 30000 milliamps.
    1.3.6.1.4.1.5528.30.10.44 netBotz-prd-bot-amps-total 1 1 The total of the readings of all amperage probes, in milliamps.
    1.3.6.1.4.1.5528.30.10.45 netBotz-prd-bot-amps-total-enabled 1 1 Total amperage alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.46 netBotz-prd-bot-amps-total-min 1 1 The total amperage minimum, from 0 to 90000 milliamps.
    1.3.6.1.4.1.5528.30.10.47 netBotz-prd-bot-amps-total-max 1 1 The total amperage maximum, from 0 to 90000 milliamps.
    1.3.6.1.4.1.5528.30.10.48 netBotz-prd-bot-amps-total-support-enabled 1 1 Total Amperage Support enabled(Y) or disabled(N).
    1.3.6.1.4.1.5528.30.10.49 netBotz-prd-bot-amps1-uV-per-10mA 1 1 The scaling factor used for the first amperage probe to convert microvolts measured from the
    Amp Detect into 10s of milliamps of…
    1.3.6.1.4.1.5528.30.10.50 netBotz-prd-bot-amps2-uV-per-10mA 1 1 The scaling factor used for the second amperage probe to convert microvolts measured from the
    Amp Detect into 10s of milliamps o…
    1.3.6.1.4.1.5528.30.10.51 netBotz-prd-bot-amps3-uV-per-mA 1 1 The scaling factor used for the third amperage probe to convert microvolts measured from the
    Amp Detect into 10s of milliamps of…
    1.3.6.1.4.1.5528.30.10.52 netBotz-prd-bot-amps1-max-range 1 1 The maximum RMS milliamps measureable by the first Amp Detect.
    1.3.6.1.4.1.5528.30.10.53 netBotz-prd-bot-amps2-max-range 1 1 The maximum RMS milliamps measureable by the second Amp Detect.
    1.3.6.1.4.1.5528.30.10.54 netBotz-prd-bot-amps3-max-range 1 1 The maximum RMS milliamps measureable by the third Amp Detect.
    1.3.6.1.4.1.5528.30.10.55 netBotz-prd-bot-amps4 1 1 The reading of the fourth amperage probe, in milliamps.
    1.3.6.1.4.1.5528.30.10.56 netBotz-prd-bot-amps4-enabled 1 1 Amperage[4] probe alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.57 netBotz-prd-bot-amps4-min 1 1 The amperage[4] probe minimum, in milliamps.
    1.3.6.1.4.1.5528.30.10.58 netBotz-prd-bot-amps4-max 1 1 The amperage[4] probe maximum, in milliamps.
    1.3.6.1.4.1.5528.30.10.60 netBotz-prd-bot-amps4-uV-per-10mA 1 1 The scaling factor used for the fourth amperage probe to convert microvolts measured from the
    Amp Detect into 10s of milliamps o…
    1.3.6.1.4.1.5528.30.10.61 netBotz-prd-bot-amps4-max-range 1 1 The maximum RMS milliamps measureable by the fourth Amp Detect.
    1.3.6.1.4.1.5528.30.10.62 netBotz-prd-bot-ext-temp1 1 1 The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.63 netBotz-prd-bot-ext-temp2 1 1 The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.64 netBotz-prd-bot-ext-temp3 1 1 The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.65 netBotz-prd-bot-ext-temp4 1 1 The reading of the external temperature probe on port 4, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.66 netBotz-prd-bot-ext-temp1-enabled 1 1 External temperature probe on port 1 alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.67 netBotz-prd-bot-ext-temp1-min 1 1 The external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.68 netBotz-prd-bot-ext-temp1-max 1 1 The external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.69 netBotz-prd-bot-ext-temp2-enabled 1 1 External temperature probe on port 2 alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.70 netBotz-prd-bot-ext-temp2-min 1 1 The external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.71 netBotz-prd-bot-ext-temp2-max 1 1 The external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.72 netBotz-prd-bot-ext-temp3-enabled 1 1 External temperature probe on port 3 alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.73 netBotz-prd-bot-ext-temp3-min 1 1 The external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.74 netBotz-prd-bot-ext-temp3-max 1 1 The external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.75 netBotz-prd-bot-ext-temp4-enabled 1 1 External temperature probe on port 4 alarm enabled(1) or disabled(0).
    1.3.6.1.4.1.5528.30.10.76 netBotz-prd-bot-ext-temp4-min 1 1 The external temperature probe on port 4 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.77 netBotz-prd-bot-ext-temp4-max 1 1 The external temperature probe on port 4 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
    1.3.6.1.4.1.5528.30.10.78 netBotz-prd-bot-ext-temp1-uV-per-degreeC 1 1 The scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the
    temperature sensor …
    1.3.6.1.4.1.5528.30.10.79 netBotz-prd-bot-ext-temp1-uV-at-0-degreeC 1 1 The offset used for the external temperature probe on port 1 of microvolts measured from the
    temperature sensor at zero degrees …
    1.3.6.1.4.1.5528.30.10.80 netBotz-prd-bot-ext-temp1-min-range 1 1 The minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C.
    Needs to be set base…
    1.3.6.1.4.1.5528.30.10.81 netBotz-prd-bot-ext-temp1-max-range 1 1 The maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C.
    Needs to be set base…
    1.3.6.1.4.1.5528.30.10.82 netBotz-prd-bot-ext-temp2-uV-per-degreeC 1 1 The scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the
    temperature sensor …
    1.3.6.1.4.1.5528.30.10.83 netBotz-prd-bot-ext-temp2-uV-at-0-degreeC 1 1 The offset used for the external temperature probe on port 2 of microvolts measured from the
    temperature sensor at zero degrees …
    1.3.6.1.4.1.5528.30.10.84 netBotz-prd-bot-ext-temp2-min-range 1 1 The minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C.
    Needs to be set base…
    1.3.6.1.4.1.5528.30.10.85 netBotz-prd-bot-ext-temp2-max-range 1 1 The maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C.
    Needs to be set base…
    1.3.6.1.4.1.5528.30.10.86 netBotz-prd-bot-ext-temp3-uV-per-degreeC 1 1 The scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the
    temperature sensor …
    1.3.6.1.4.1.5528.30.10.87 netBotz-prd-bot-ext-temp3-uV-at-0-degreeC 1 1 The offset used for the external temperature probe on port 3 of microvolts measured from the
    temperature sensor at zero degrees …
    1.3.6.1.4.1.5528.30.10.88 netBotz-prd-bot-ext-temp3-min-range 1 1 The minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C.
    Needs to be set base…
    1.3.6.1.4.1.5528.30.10.89 netBotz-prd-bot-ext-temp3-max-range 1 1 The maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C.
    Needs to be set base…
    1.3.6.1.4.1.5528.30.10.90 netBotz-prd-bot-ext-temp4-uV-per-degreeC 1 1 The scaling factor used for the external temperature probe on port 4 to convert microvolts measured from the
    temperature sensor …
    ...