Reference record for OID 1.3.6.1.4.1.476.1.42.3.8.30.40.1.5



parent
1.3.6.1.4.1.476.1.42.3.8.30.40.1 (lgpPduPsLineEntry)
node code
5
node name
lgpPduPsLineEntryIndex
dot oid
1.3.6.1.4.1.476.1.42.3.8.30.40.1.5
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsLineTable(40) lgpPduPsLineEntry(1) lgpPduPsLineEntryIndex(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsLineTable(40) lgpPduPsLineEntry(1) lgpPduPsLineEntryIndex(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsLineTable(40) lgpPduPsLineEntry(1) lgpPduPsLineEntryIndex(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsLineTable(40) lgpPduPsLineEntry(1) lgpPduPsLineEntryIndex(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsLineTable(40) lgpPduPsLineEntry(1) lgpPduPsLineEntryIndex(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsLineTable(40) lgpPduPsLineEntry(1) lgpPduPsLineEntryIndex(5)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsLineTable/lgpPduPsLineEntry/lgpPduPsLineEntryIndex
  • /iso/identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsLineTable/lgpPduPsLineEntry/lgpPduPsLineEntryIndex
  • /iso/org/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsLineTable/lgpPduPsLineEntry/lgpPduPsLineEntryIndex
  • /iso/org/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsLineTable/lgpPduPsLineEntry/lgpPduPsLineEntryIndex
  • /iso/iso-identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsLineTable/lgpPduPsLineEntry/lgpPduPsLineEntryIndex
  • /iso/iso-identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsLineTable/lgpPduPsLineEntry/lgpPduPsLineEntryIndex
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/476/1/42/3/8/30/40/1/5

    Description by mibdepot

    This is the index that indicates the line/phase of the measurements
    in the given row of the 'lgpPduPsLineTable'.

    Parsed from file LIEBERT_GP_PDU.MIB.txt
    Company: liebert
    Module: LIEBERT-GP-PDU-MIB

    Information by oid_info

    Vendor: Liebert
    Module: LIEBERT-GP-PDU-MIB (LIEBERT_GP_PDU.MIB)
    Type: TABULAR
    Access: not-accessible
    Syntax: Unsigned32

    Automatically extracted from www.mibdepot.com

    Information by mibdepot

    lgpPduPsLineEntryIndex OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "This is the index that indicates the line/phase of the measurements in the given row of the 'lgpPduPsLineTable'." ::= { lgpPduPsLineEntry 5 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.476)

    [email protected]

    Brothers (14)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.10 lgpPduPsLineEntryId 0 0 Unique identifier (within a PDU) for the PDU's power source.
    The object may not be available in non-modular systems.
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.15 lgpPduPsLineEntryLine 0 0 The line number (phase) that the measurement represents for all
    measurements in a given row of the table. Note that this always…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.19 lgpPduPsLineEntryEpLNTenths 0 0 Alternating Current RMS Line to Neutral Electrical Potential
    measurement.
    The line/phase being measured is indicated by the corre…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.20 lgpPduPsLineEntryEpLN 0 0 Alternating Current RMS Line to Neutral Electrical Potential
    measurement.
    The line/phase being measured is indicated by the corre…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.21 lgpPduPsLineEntryEc 0 0 Total input line-to-neutral electrical current.
    The line/phase being measured is indicated by the corresponding
    lgpPduPsLineEntry…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.22 lgpPduPsLineEntryEcHundredths 0 0 Total input line-to-neutral electrical current.
    The line/phase being measured is indicated by the corresponding
    lgpPduPsLineEntry…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.35 lgpPduPsLineEntryEcThrshldUndrAlarm 0 0 The threshold at which an under current alarm is activated. If
    the measured current (lgpPduPsLineEntryEc) is equal to or below
    t…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.36 lgpPduPsLineEntryEcThrshldOvrWarn 0 0 The threshold at which an over current warning is activated. If
    the measured current (lgpPduPsLineEntryEc) is equal to or over
    t…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.37 lgpPduPsLineEntryEcThrshldOvrAlarm 0 0 The threshold at which an over current alarm is activated. If
    the measured current (lgpPduPsLineEntryEc) is equal to or over
    thi…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.38 lgpPduPsLineEntryEcAvailBeforeAlarm 0 0 The amount that the current/amperage may increase from its present
    value before an over current alarm occurs.
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.39 lgpPduPsLineEntryEcUsedBeforeAlarm 0 0 The percent of current utilization relative to the over current
    alarm threshold.
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.60 lgpPduPsLineEntryEpLL 0 0 Line to Line Electrical Potential.
    The line/phase being measured is indicated by the corresponding
    lgpPduPsLineEntryLine value of…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.61 lgpPduPsLineEntryEpLLTenths 0 0 Line to Line Electrical Potential.
    The line/phase being measured is indicated by the corresponding
    lgpPduPsLineEntryLine value of…
    1.3.6.1.4.1.476.1.42.3.8.30.40.1.62 lgpPduPsLineEntryEcAvailBeforeAlarmHundredths 0 0 The amount that the current/amperage may increase from its present
    value before an over current alarm occurs.