Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state. The ON/OFF switch on the UPS
must be toggled for the UPS to return to operation.
Setting this variable to turnUpsOffGracefully(3) causes
the UPS to shut off after a delay period. This allows the
host to shut down in a graceful manner. When in this state,
the UPS will not provide output power regardless of the
input line state. The ON/OFF switch on the UPS
must be toggled for the UPS to return to operation.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state.
Setting this variable to turnUpsOffGracefully(3) causes
the UPS to shut off after a delay period. This allows the
host to shut down in a graceful manner. When in this state,
the UPS will not provide output power regardless of the
input line state.
If this UPS is an active member of a Synchronized
Control Group (SCG) the turnUpsSyncGroupOff(4) command
will perform a Synchronized Turn Off of all active Group
members regardless of their current AC output status.
If this UPS is an active member of a Synchronized
Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5)
command will perform a Synchronized Turn Off After Delay
of all active Group members regardless of their current
AC output status. This unit's Shutdown Delay will be used
to execute the Turn Off After Delay command.
If this UPS is an active member of an SCG, the
turnUpsSyncGroupOffGracefully(6) command will perform a
Synchronized Turn Off Gracefully of all active Group
members regardless of their current AC output status.
This unit's Maximum Shutdown Time and Shutdown Delay will
be used to execute the Turn Off Gracefully command.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvControlUpsOff OBJECT-TYPE SYNTAX INTEGER { noTurnUpsOff(1), turnUpsOff(2), turnUpsOffGracefully(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. The ON/OFF switch on the UPS must be toggled for the UPS to return to operation. Setting this variable to turnUpsOffGracefully(3) causes the UPS to shut off after a delay period. This allows the host to shut down in a graceful manner. When in this state, the UPS will not provide output power regardless of the input line state. The ON/OFF switch on the UPS must be toggled for the UPS to return to operation. Setting this value to noTurnUpsOff(1) has no effect. The value noTurnUpsOff(1) will always be returned when the variable is read." ::= { upsAdvControl 1 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvControlUpsOff OBJECT-TYPE SYNTAX INTEGER { noTurnUpsOff(1), turnUpsOff(2), turnUpsOffGracefully(3), turnUpsSyncGroupOff(4), turnUpsSyncGroupOffAfterDelay(5), turnUpsSyncGroupOffGracefully(6) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. Setting this variable to turnUpsOffGracefully(3) causes the UPS to shut off after a delay period. This allows the host to shut down in a graceful manner. When in this state, the UPS will not provide output power regardless of the input line state. If this UPS is an active member of a Synchronized Control Group (SCG) the turnUpsSyncGroupOff(4) command will perform a Synchronized Turn Off of all active Group members regardless of their current AC output status. If this UPS is an active member of a Synchronized Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5) command will perform a Synchronized Turn Off After Delay of all active Group members regardless of their current AC output status. This unit's Shutdown Delay will be used to execute the Turn Off After Delay command. If this UPS is an active member of an SCG, the turnUpsSyncGroupOffGracefully(6) command will perform a Synchronized Turn Off Gracefully of all active Group members regardless of their current AC output status. This unit's Maximum Shutdown Time and Shutdown Delay will be used to execute the Turn Off Gracefully command. Setting this value to noTurnUpsOff(1) has no effect. The value noTurnUpsOff(1) will always be returned when the variable is read." ::= { upsAdvControl 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.1.0 | upsAdvControlUpsOff | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.2 | upsAdvControlRebootShutdownUps, upsAdvControlRebootUps | 1 | 1 | Setting this value to noRebootUps(1) has no effect. Setting this variable to rebootUps(2) causes the UPS to shut off and turn bac… |
1.3.6.1.4.1.318.1.1.1.6.2.3 | upsAdvControlUpsSleep | 1 | 1 | Setting this value to noPutUpsToSleep(1) has no effect. Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep f… |
1.3.6.1.4.1.318.1.1.1.6.2.4 | upsAdvControlSimulatePowerFail | 1 | 1 | Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFai… |
1.3.6.1.4.1.318.1.1.1.6.2.5 | upsAdvControlFlashAndBeep | 1 | 1 | Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS … |
1.3.6.1.4.1.318.1.1.1.6.2.6 | upsAdvControlTurnOnUPS | 1 | 1 | Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately, provided upsBasicOutputStatus does not read ON.… |
1.3.6.1.4.1.318.1.1.1.6.2.7 | upsAdvControlBypassSwitch | 1 | 1 | This switch puts the UPS in or out of bypass mode. |
1.3.6.1.4.1.318.1.1.1.6.2.8 | upsAdvControlRebootUpsWithOrWithoutAC | 1 | 1 | Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time… |
1.3.6.1.4.1.318.1.1.1.6.2.9 | upsAdvControlFirmwareUpdate | 1 | 1 | Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwa… |