Setting this value to noRebootUps(1) has no effect.
Setting this variable to rebootUps(2) causes the
UPS to shut off and turn back on.
Setting this variable to rebootUpsGracefully(3) causes the
UPS to shut off and turn back on after a delay period.
This allows the host to shut down in a graceful manner.
The value noRebootUps(1) will always be returned
when the variable is read.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Setting this variable to rebootShutdownUps(2) causes the UPS
to shut off and turn back on (as long as good AC input power
is available, otherwise the UPS will remain off until good AC
input power is available).
Setting this variable to rebootShutdownUpsGracefully(3) causes
the UPS to shut off after a delay period and then turn back
on. This allows the host to shut down in a graceful manner.
If this UPS is an active member of a Synchronized Control
Group (SCG) the rebootShutdownSyncGroupUps(4) command will
perform a Synchronized Reboot of all active Group members
regardless of their current AC output status. If applicable,
this unit's Power Synchronization Delay, Shutdown Delay,
Return Delay, Return Battery Capacity, and Return Battery
Capacity Offset will be used to execute the Reboot command.
If this UPS is an active member of a SCG the
rebootShutdownSyncGroupUpsGracefully(5) command will perform
a Synchronized Reboot of all active Group members regardless
of their current AC output status. If applicable, this unit's
Power Synchronization Delay, Maximum Shutdown Time, Shutdown
Delay, Return Delay, Return Battery Capacity, and Return
Battery Capacity Offset will be used to execute the Reboot
command.
Setting this value to noRebootShutdownUps(1) has no effect.
The value noRebootShutdownUps(1) will always be returned when
the variable is read.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvControlRebootUps OBJECT-TYPE SYNTAX INTEGER { noRebootUps(1), rebootUps(2), rebootUpsGracefully(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this value to noRebootUps(1) has no effect. Setting this variable to rebootUps(2) causes the UPS to shut off and turn back on. Setting this variable to rebootUpsGracefully(3) causes the UPS to shut off and turn back on after a delay period. This allows the host to shut down in a graceful manner. The value noRebootUps(1) will always be returned when the variable is read." ::= { upsAdvControl 2 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvControlRebootShutdownUps OBJECT-TYPE SYNTAX INTEGER { noRebootShutdownUps(1), rebootShutdownUps(2), rebootShutdownUpsGracefully(3), rebootShutdownSyncGroupUps(4), rebootShutdownSyncGroupUpsGracefully(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to rebootShutdownUps(2) causes the UPS to shut off and turn back on (as long as good AC input power is available, otherwise the UPS will remain off until good AC input power is available). Setting this variable to rebootShutdownUpsGracefully(3) causes the UPS to shut off after a delay period and then turn back on. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG) the rebootShutdownSyncGroupUps(4) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. If applicable, this unit's Power Synchronization Delay, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. If this UPS is an active member of a SCG the rebootShutdownSyncGroupUpsGracefully(5) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. If applicable, this unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. Setting this value to noRebootShutdownUps(1) has no effect. The value noRebootShutdownUps(1) will always be returned when the variable is read." ::= { upsAdvControl 2 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.2.0 | upsAdvControlRebootUps | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.1 | upsAdvControlUpsOff | 1 | 1 | Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power reg… |
1.3.6.1.4.1.318.1.1.1.6.2.3 | upsAdvControlUpsSleep | 1 | 1 | Setting this value to noPutUpsToSleep(1) has no effect. Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep f… |
1.3.6.1.4.1.318.1.1.1.6.2.4 | upsAdvControlSimulatePowerFail | 1 | 1 | Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFai… |
1.3.6.1.4.1.318.1.1.1.6.2.5 | upsAdvControlFlashAndBeep | 1 | 1 | Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS … |
1.3.6.1.4.1.318.1.1.1.6.2.6 | upsAdvControlTurnOnUPS | 1 | 1 | Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately, provided upsBasicOutputStatus does not read ON.… |
1.3.6.1.4.1.318.1.1.1.6.2.7 | upsAdvControlBypassSwitch | 1 | 1 | This switch puts the UPS in or out of bypass mode. |
1.3.6.1.4.1.318.1.1.1.6.2.8 | upsAdvControlRebootUpsWithOrWithoutAC | 1 | 1 | Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time… |
1.3.6.1.4.1.318.1.1.1.6.2.9 | upsAdvControlFirmwareUpdate | 1 | 1 | Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwa… |