Reference record for OID 1.3.6.1.4.1.318.1.1.1.6.2.9



parent
1.3.6.1.4.1.318.1.1.1.6.2 (upsAdvControl)
node code
9
node name
upsAdvControlFirmwareUpdate
dot oid
1.3.6.1.4.1.318.1.1.1.6.2.9
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlFirmwareUpdate(9)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlFirmwareUpdate(9)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlFirmwareUpdate(9)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlFirmwareUpdate(9)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlFirmwareUpdate(9)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlFirmwareUpdate(9)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlFirmwareUpdate
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlFirmwareUpdate
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlFirmwareUpdate
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlFirmwareUpdate
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlFirmwareUpdate
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlFirmwareUpdate
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/1/6/2/9

    Description by mibdepot

    Setting this variable to firmwareUpdate(2) causes the
    UPS to begin a firmware update if possible.

    Setting this value to noFirmwareUpdate(1) will clear the
    previous results, if any, or otherwise has no effect.

    Reading this variable will return noFirmwareUpdate(1) when
    the UPS firmware has not been updated (or previous results
    have been cleared), updateInProcess(3) when the UPS firmware
    is being updated, updateSuccessful(4) when the UPS firmware
    has been successfully updated, or updateFailed(5) if the UPS
    firmware update failed.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    Setting this variable to firmwareUpdate(2) causes the
    UPS to begin a firmware update if possible.

    Setting this value to noFirmwareUpdate(1) will clear the
    previous results, if any, or otherwise has no effect.

    Reading this variable will return noFirmwareUpdate(1) when
    the UPS firmware has not been updated (or previous results
    have been cleared), updateInProcess(3) when the UPS firmware
    is being updated, updateSuccessful(4) when the UPS firmware
    has been successfully updated, or updateFailed(5) if the UPS
    firmware update failed.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    upsAdvControlFirmwareUpdate OBJECT-TYPE SYNTAX INTEGER { noFirmwareUpdate (1), firmwareUpdate (2), updateInProcess (3), updateSuccessful (4), updateFailed (5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwareUpdate(1) will clear the previous results, if any, or otherwise has no effect. Reading this variable will return noFirmwareUpdate(1) when the UPS firmware has not been updated (or previous results have been cleared), updateInProcess(3) when the UPS firmware is being updated, updateSuccessful(4) when the UPS firmware has been successfully updated, or updateFailed(5) if the UPS firmware update failed." ::= { upsAdvControl 9 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    upsAdvControlFirmwareUpdate OBJECT-TYPE SYNTAX INTEGER { noFirmwareUpdate (1), firmwareUpdate (2), updateInProcess (3), updateSuccessful (4), updateFailed (5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwareUpdate(1) will clear the previous results, if any, or otherwise has no effect. Reading this variable will return noFirmwareUpdate(1) when the UPS firmware has not been updated (or previous results have been cleared), updateInProcess(3) when the UPS firmware is being updated, updateSuccessful(4) when the UPS firmware has been successfully updated, or updateFailed(5) if the UPS firmware update failed." ::= { upsAdvControl 9 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.6.2.9.0 upsAdvControlFirmwareUpdate 0 0 None

    Brothers (8)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.6.2.1 upsAdvControlUpsOff 1 1 Setting this variable to turnUpsOff(2) causes
    the UPS to shut off. When in this state, the UPS
    will not provide output power reg…
    1.3.6.1.4.1.318.1.1.1.6.2.2 upsAdvControlRebootShutdownUps, upsAdvControlRebootUps 1 1 Setting this value to noRebootUps(1) has no effect.

    Setting this variable to rebootUps(2) causes the
    UPS to shut off and turn bac…
    1.3.6.1.4.1.318.1.1.1.6.2.3 upsAdvControlUpsSleep 1 1 Setting this value to noPutUpsToSleep(1) has no
    effect.

    Setting this variable to putUpsToSleep(2) causes
    the UPS to go to sleep f…
    1.3.6.1.4.1.318.1.1.1.6.2.4 upsAdvControlSimulatePowerFail 1 1 Setting this variable to simulatePowerFailure(2) causes
    the UPS switch to battery power.

    Setting this value to noSimulatePowerFai…
    1.3.6.1.4.1.318.1.1.1.6.2.5 upsAdvControlFlashAndBeep 1 1 Setting this variable to flashAndBeep(2) causes the
    UPS to beep and simultaneously turn on the UPS front
    panel lights (Smart-UPS …
    1.3.6.1.4.1.318.1.1.1.6.2.6 upsAdvControlTurnOnUPS 1 1 Setting this variable to turnOnUPS(2) causes the
    UPS to be turned on immediately, provided
    upsBasicOutputStatus does not read ON.…
    1.3.6.1.4.1.318.1.1.1.6.2.7 upsAdvControlBypassSwitch 1 1 This switch puts the UPS in or out of bypass mode.
    1.3.6.1.4.1.318.1.1.1.6.2.8 upsAdvControlRebootUpsWithOrWithoutAC 1 1 Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
    causes the UPS to turn off immediately, wait for a minimum time…