Setting this variable to firmwareUpdate(2) causes the
UPS to begin a firmware update if possible.
Setting this value to noFirmwareUpdate(1) will clear the
previous results, if any, or otherwise has no effect.
Reading this variable will return noFirmwareUpdate(1) when
the UPS firmware has not been updated (or previous results
have been cleared), updateInProcess(3) when the UPS firmware
is being updated, updateSuccessful(4) when the UPS firmware
has been successfully updated, or updateFailed(5) if the UPS
firmware update failed.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Setting this variable to firmwareUpdate(2) causes the
UPS to begin a firmware update if possible.
Setting this value to noFirmwareUpdate(1) will clear the
previous results, if any, or otherwise has no effect.
Reading this variable will return noFirmwareUpdate(1) when
the UPS firmware has not been updated (or previous results
have been cleared), updateInProcess(3) when the UPS firmware
is being updated, updateSuccessful(4) when the UPS firmware
has been successfully updated, or updateFailed(5) if the UPS
firmware update failed.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvControlFirmwareUpdate OBJECT-TYPE SYNTAX INTEGER { noFirmwareUpdate (1), firmwareUpdate (2), updateInProcess (3), updateSuccessful (4), updateFailed (5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwareUpdate(1) will clear the previous results, if any, or otherwise has no effect. Reading this variable will return noFirmwareUpdate(1) when the UPS firmware has not been updated (or previous results have been cleared), updateInProcess(3) when the UPS firmware is being updated, updateSuccessful(4) when the UPS firmware has been successfully updated, or updateFailed(5) if the UPS firmware update failed." ::= { upsAdvControl 9 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvControlFirmwareUpdate OBJECT-TYPE SYNTAX INTEGER { noFirmwareUpdate (1), firmwareUpdate (2), updateInProcess (3), updateSuccessful (4), updateFailed (5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwareUpdate(1) will clear the previous results, if any, or otherwise has no effect. Reading this variable will return noFirmwareUpdate(1) when the UPS firmware has not been updated (or previous results have been cleared), updateInProcess(3) when the UPS firmware is being updated, updateSuccessful(4) when the UPS firmware has been successfully updated, or updateFailed(5) if the UPS firmware update failed." ::= { upsAdvControl 9 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.9.0 | upsAdvControlFirmwareUpdate | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.1 | upsAdvControlUpsOff | 1 | 1 | Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power reg… |
1.3.6.1.4.1.318.1.1.1.6.2.2 | upsAdvControlRebootShutdownUps, upsAdvControlRebootUps | 1 | 1 | Setting this value to noRebootUps(1) has no effect. Setting this variable to rebootUps(2) causes the UPS to shut off and turn bac… |
1.3.6.1.4.1.318.1.1.1.6.2.3 | upsAdvControlUpsSleep | 1 | 1 | Setting this value to noPutUpsToSleep(1) has no effect. Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep f… |
1.3.6.1.4.1.318.1.1.1.6.2.4 | upsAdvControlSimulatePowerFail | 1 | 1 | Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFai… |
1.3.6.1.4.1.318.1.1.1.6.2.5 | upsAdvControlFlashAndBeep | 1 | 1 | Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS … |
1.3.6.1.4.1.318.1.1.1.6.2.6 | upsAdvControlTurnOnUPS | 1 | 1 | Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately, provided upsBasicOutputStatus does not read ON.… |
1.3.6.1.4.1.318.1.1.1.6.2.7 | upsAdvControlBypassSwitch | 1 | 1 | This switch puts the UPS in or out of bypass mode. |
1.3.6.1.4.1.318.1.1.1.6.2.8 | upsAdvControlRebootUpsWithOrWithoutAC | 1 | 1 | Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time… |