Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately, provided
upsBasicOutputStatus does not read ON.
Setting this value to noTurnOnUPS(1) has no
effect.
The value noTurnOnUPS(1) will always be returned
when the variable is read.
This action is only available with the APC
Mini-SNMP Adapter.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately.
If this UPS is an active member of a Synchronized Control
Group (SCG), the turnOnUPSSyncGroup(3) command will perform
a Synchronized Turn On of all active Group members
regardless of their current AC output status.
Setting this value to noTurnOnUPS(1) has no
effect.
The value noTurnOnUPS(1) will always be returned
when the variable is read.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvControlTurnOnUPS OBJECT-TYPE SYNTAX INTEGER { noTurnOnUPS(1), turnOnUPS(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately, provided upsBasicOutputStatus does not read ON. Setting this value to noTurnOnUPS(1) has no effect. The value noTurnOnUPS(1) will always be returned when the variable is read. This action is only available with the APC Mini-SNMP Adapter." ::= { upsAdvControl 6 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvControlTurnOnUPS OBJECT-TYPE SYNTAX INTEGER { noTurnOnUPS(1), turnOnUPS(2), turnOnUPSSyncGroup(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately. If this UPS is an active member of a Synchronized Control Group (SCG), the turnOnUPSSyncGroup(3) command will perform a Synchronized Turn On of all active Group members regardless of their current AC output status. Setting this value to noTurnOnUPS(1) has no effect. The value noTurnOnUPS(1) will always be returned when the variable is read." ::= { upsAdvControl 6 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.6.0 | upsAdvControlTurnOnUPS | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.1 | upsAdvControlUpsOff | 1 | 1 | Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power reg… |
1.3.6.1.4.1.318.1.1.1.6.2.2 | upsAdvControlRebootShutdownUps, upsAdvControlRebootUps | 1 | 1 | Setting this value to noRebootUps(1) has no effect. Setting this variable to rebootUps(2) causes the UPS to shut off and turn bac… |
1.3.6.1.4.1.318.1.1.1.6.2.3 | upsAdvControlUpsSleep | 1 | 1 | Setting this value to noPutUpsToSleep(1) has no effect. Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep f… |
1.3.6.1.4.1.318.1.1.1.6.2.4 | upsAdvControlSimulatePowerFail | 1 | 1 | Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFai… |
1.3.6.1.4.1.318.1.1.1.6.2.5 | upsAdvControlFlashAndBeep | 1 | 1 | Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS … |
1.3.6.1.4.1.318.1.1.1.6.2.7 | upsAdvControlBypassSwitch | 1 | 1 | This switch puts the UPS in or out of bypass mode. |
1.3.6.1.4.1.318.1.1.1.6.2.8 | upsAdvControlRebootUpsWithOrWithoutAC | 1 | 1 | Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time… |
1.3.6.1.4.1.318.1.1.1.6.2.9 | upsAdvControlFirmwareUpdate | 1 | 1 | Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwa… |