Reference record for OID 1.3.6.1.4.1.318.1.1.1.6.2.3



parent
1.3.6.1.4.1.318.1.1.1.6.2 (upsAdvControl)
node code
3
node name
upsAdvControlUpsSleep
dot oid
1.3.6.1.4.1.318.1.1.1.6.2.3
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlUpsSleep(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlUpsSleep(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsControl(6) upsAdvControl(2) upsAdvControlUpsSleep(3)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlUpsSleep
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlUpsSleep
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlUpsSleep
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlUpsSleep
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsControl/upsAdvControl/upsAdvControlUpsSleep
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/1/6/2/3

    Description by mibdepot

    Setting this value to noPutUpsToSleep(1) has no
    effect.

    Setting this variable to putUpsToSleep(2) causes
    the UPS to go to sleep for the time specified by
    upsAdvConfigUpsSleepTime.

    Setting this variable to putUpsToSleepGracefully(3)
    causes the UPS to go to sleep for the time specified
    by upsAdvConfigUpsSleepTime after a delay period.
    This allows the host to shut down in a graceful manner.

    When in sleep mode, the UPS will not provide output
    power regardless of the input line state. Once the
    specified time has elapsed, output power will be
    restored.

    The value noPutUpsToSleep(1) will always be returned
    when the variable is read.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    Setting this variable to putUpsToSleep(2) causes
    the UPS to go to sleep for the time specified by
    upsAdvConfigUpsSleepTime.

    Setting this variable to putUpsToSleepGracefully(3)
    causes the UPS to go to sleep for the time specified
    by upsAdvConfigUpsSleepTime after a delay period.
    This allows the host to shut down in a graceful manner.

    If this UPS is an active member of a Synchronized Control
    Group (SCG), the putUpsSyncGroupToSleep(4) command will perform
    a Synchronized Sleep of all active Group members regardless
    of their current AC output status. This unit's Power
    Synchronization Delay, Shutdown Delay, Sleep Time,
    and Return Delay will be used to execute the sleep command.

    If this UPS is an active member of a SCG the
    putUpsSyncGroupToSleepGracefully(5) command will perform a
    Synchronized Sleep Gracefully of all active Group members
    regardless of their current AC output status. This unit's
    Power Synchronization Delay, Maximum Shutdown Time, Shutdown
    Delay, Sleep Time, and Return Delay to execute the sleep
    command.

    When in sleep mode, the UPS will not provide output
    power regardless of the input line state. Once the
    specified time has elapsed, output power will be
    restored.

    Setting this value to noPutUpsToSleep(1) has no
    effect.

    The value noPutUpsToSleep(1) will always be returned
    when the variable is read.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    upsAdvControlUpsSleep OBJECT-TYPE SYNTAX INTEGER { noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this value to noPutUpsToSleep(1) has no effect. Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. The value noPutUpsToSleep(1) will always be returned when the variable is read." ::= { upsAdvControl 3 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    upsAdvControlUpsSleep OBJECT-TYPE SYNTAX INTEGER { noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3), putUpsSyncGroupToSleep(4), putUpsSyncGroupToSleepGracefully(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG), the putUpsSyncGroupToSleep(4) command will perform a Synchronized Sleep of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Shutdown Delay, Sleep Time, and Return Delay will be used to execute the sleep command. If this UPS is an active member of a SCG the putUpsSyncGroupToSleepGracefully(5) command will perform a Synchronized Sleep Gracefully of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Sleep Time, and Return Delay to execute the sleep command. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read." ::= { upsAdvControl 3 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.6.2.3.0 upsAdvControlUpsSleep 0 0 None

    Brothers (8)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.6.2.1 upsAdvControlUpsOff 1 1 Setting this variable to turnUpsOff(2) causes
    the UPS to shut off. When in this state, the UPS
    will not provide output power reg…
    1.3.6.1.4.1.318.1.1.1.6.2.2 upsAdvControlRebootShutdownUps, upsAdvControlRebootUps 1 1 Setting this value to noRebootUps(1) has no effect.

    Setting this variable to rebootUps(2) causes the
    UPS to shut off and turn bac…
    1.3.6.1.4.1.318.1.1.1.6.2.4 upsAdvControlSimulatePowerFail 1 1 Setting this variable to simulatePowerFailure(2) causes
    the UPS switch to battery power.

    Setting this value to noSimulatePowerFai…
    1.3.6.1.4.1.318.1.1.1.6.2.5 upsAdvControlFlashAndBeep 1 1 Setting this variable to flashAndBeep(2) causes the
    UPS to beep and simultaneously turn on the UPS front
    panel lights (Smart-UPS …
    1.3.6.1.4.1.318.1.1.1.6.2.6 upsAdvControlTurnOnUPS 1 1 Setting this variable to turnOnUPS(2) causes the
    UPS to be turned on immediately, provided
    upsBasicOutputStatus does not read ON.…
    1.3.6.1.4.1.318.1.1.1.6.2.7 upsAdvControlBypassSwitch 1 1 This switch puts the UPS in or out of bypass mode.
    1.3.6.1.4.1.318.1.1.1.6.2.8 upsAdvControlRebootUpsWithOrWithoutAC 1 1 Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2)
    causes the UPS to turn off immediately, wait for a minimum time…
    1.3.6.1.4.1.318.1.1.1.6.2.9 upsAdvControlFirmwareUpdate 1 1 Setting this variable to firmwareUpdate(2) causes the
    UPS to begin a firmware update if possible.

    Setting this value to noFirmwa…