Setting this value to noPutUpsToSleep(1) has no
effect.
Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
Setting this variable to putUpsToSleepGracefully(3)
causes the UPS to go to sleep for the time specified
by upsAdvConfigUpsSleepTime after a delay period.
This allows the host to shut down in a graceful manner.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
The value noPutUpsToSleep(1) will always be returned
when the variable is read.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
Setting this variable to putUpsToSleepGracefully(3)
causes the UPS to go to sleep for the time specified
by upsAdvConfigUpsSleepTime after a delay period.
This allows the host to shut down in a graceful manner.
If this UPS is an active member of a Synchronized Control
Group (SCG), the putUpsSyncGroupToSleep(4) command will perform
a Synchronized Sleep of all active Group members regardless
of their current AC output status. This unit's Power
Synchronization Delay, Shutdown Delay, Sleep Time,
and Return Delay will be used to execute the sleep command.
If this UPS is an active member of a SCG the
putUpsSyncGroupToSleepGracefully(5) command will perform a
Synchronized Sleep Gracefully of all active Group members
regardless of their current AC output status. This unit's
Power Synchronization Delay, Maximum Shutdown Time, Shutdown
Delay, Sleep Time, and Return Delay to execute the sleep
command.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvControlUpsSleep OBJECT-TYPE SYNTAX INTEGER { noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this value to noPutUpsToSleep(1) has no effect. Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. The value noPutUpsToSleep(1) will always be returned when the variable is read." ::= { upsAdvControl 3 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvControlUpsSleep OBJECT-TYPE SYNTAX INTEGER { noPutUpsToSleep(1), putUpsToSleep(2), putUpsToSleepGracefully(3), putUpsSyncGroupToSleep(4), putUpsSyncGroupToSleepGracefully(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG), the putUpsSyncGroupToSleep(4) command will perform a Synchronized Sleep of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Shutdown Delay, Sleep Time, and Return Delay will be used to execute the sleep command. If this UPS is an active member of a SCG the putUpsSyncGroupToSleepGracefully(5) command will perform a Synchronized Sleep Gracefully of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Sleep Time, and Return Delay to execute the sleep command. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read." ::= { upsAdvControl 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.3.0 | upsAdvControlUpsSleep | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.6.2.1 | upsAdvControlUpsOff | 1 | 1 | Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power reg… |
1.3.6.1.4.1.318.1.1.1.6.2.2 | upsAdvControlRebootShutdownUps, upsAdvControlRebootUps | 1 | 1 | Setting this value to noRebootUps(1) has no effect. Setting this variable to rebootUps(2) causes the UPS to shut off and turn bac… |
1.3.6.1.4.1.318.1.1.1.6.2.4 | upsAdvControlSimulatePowerFail | 1 | 1 | Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFai… |
1.3.6.1.4.1.318.1.1.1.6.2.5 | upsAdvControlFlashAndBeep | 1 | 1 | Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS … |
1.3.6.1.4.1.318.1.1.1.6.2.6 | upsAdvControlTurnOnUPS | 1 | 1 | Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately, provided upsBasicOutputStatus does not read ON.… |
1.3.6.1.4.1.318.1.1.1.6.2.7 | upsAdvControlBypassSwitch | 1 | 1 | This switch puts the UPS in or out of bypass mode. |
1.3.6.1.4.1.318.1.1.1.6.2.8 | upsAdvControlRebootUpsWithOrWithoutAC | 1 | 1 | Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time… |
1.3.6.1.4.1.318.1.1.1.6.2.9 | upsAdvControlFirmwareUpdate | 1 | 1 | Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwa… |